Specifications

Parameters/address space
4.2 Address space
DI 16x24VDC HF Digital Input Module (6ES7521-1BH00-0AB0)
Manual, 07/2014, A5E03485952-AD
15
Parameters
Range of values
Default
Parameter
assignment
in RUN
Scope with configuration software,
e.g., STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Hardware interrupt
Positive edge
Yes/No No Yes Channel Channel
Negative edge
Yes/No No Yes Channel Channel
Positive and negative edge
Yes/No No Yes Channel Channel
* If you enable diagnostics for multiple channels, you will receive an alarm surge on failure of the supply voltage because
each enabled channel will detect this fault.
You can prevent this message burst by
assigning the diagnostics function to one channel only.
** The scope can be assigned for each channel during parameter assignment in RUN.
4.2
Address space
The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
The letters "a to d" are printed onto the module. "IB a" for example, stands for module start
address input byte a.
Configuration options of DI 16x24VDC HF
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 2 Configuration options
Configuration
Short designation/
module name in the
GSD file
Configuration software, e.g., with STEP 7 (TIA Portal)
Integrated in hardware
catalog STEP 7
(TIA Portal)
GSD file in
STEP 7 (TIA Portal) V12 or
higher or STEP 7 V5.5 SP3
or higher
1 x 16-channel without value status
DI 16x24VDC HF
V12 or higher
X
1 x 16-channel with value status
DI 16x24VDC HF QI
V12 or higher
X
2 x 8-channel without value status DI 16x24VDC HF S V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)
2 x 8-channel with value status DI 16x24VDC HF QI
S
V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)
1 x 16-channel with value status for
module-internal shared input with up to 4
submodules
DI 16x24VDC HF MSI V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)