7 Reference
7.1 Message to Data Array Mapping
This driver was designed to be connected to the Notifier Onyx NFS-3030 printer port and listen for incoming
messages. The panel's default setting for the printer port is off. To utilize this driver, the printer must be
enabled on the unit and set to 80 columns with NO supervision unless port supervision is enabled in the
driver configuration. Refer to Section
5.1 for more information on port supervision.
The purpose of this driver is to record the status of devices connected to the NFS-3030 system by
interpreting the text messages sent to the printer port. Only messages that directly pertain to device status
are currently supported. The following subset of event messages is recognized:
7.1.1 Notifier NFS-3030 Message Types Recognized
Event Keyword
Data Arrays
Affected
Clearing Event
Notes
Fire Alarm
Modules/Detectors
Cleared Fire Alarm
System Normal
states: {0,1}
Trouble
Modules/Detectors
System
Panel Circuit
Cleared Trouble
System Normal
This is for both point and system trouble -
system troubles are only 1 line messages
with no point address.
states: {counter}
Pre Alarm
Detectors
Cleared Pre Alarm
System Normal
states: {0,1}
Security Alarm
Modules
Panel Circuit
Cleared Security
Alarm
System Normal
states: {0,1}
Supervisory
Modules
Cleared
Supervisory
System Normal
states: {0,1}
Disabled
Zones
Modules/Detectors
Panel Circuit
Cleared Disabled
System Normal
states: {0,1}
On/Off
Modules
Panel
Off/On
states: {0,1}
System Normal
All
Will reset all Data Arrays for all loops and
the system to zero
Active
Modules
Cleared Active