Specs

19
ELECTRICAL DATA
Units
Nominal
V-PH-HZ
Voltage
Range
Compressor Electrical Heat Power Supply
RLA LRA
OFM IFM Nominal FLA MCA
MOCP**
MIN MAX FLA FLA kW* 208 240 208 230
24 208/230-1-60 197 253 10.3 61.6 0.9 2.8
-/- - - 16.6 16.6 25
3.8/5 18 20.8 39.1 42.6 40/45
5.6/7.2 27 31.3 50.3 55.7 60/60
7.5/10 36.1 41.7 61.7 68.7 70/70
30 208/230-1-60 197 253 13.5 72.5 0.9 2.8
-/- - - 20.6 20.6 30
3.8/5 18 20.8 43.1 46.6 45/50
5.6/7.2 27 31.3 54.3 59.7 60/60
7.5/10 36.1 41.7 65.7 72.7 70/80
36 208/230-1-60 197 253 14.7 75.0 1.7 4.1
-/- - - 24.2 24.2 35
3.8/5 18 20.8 46.7 50.2 50/60
5.6/7.2 27 31.3 57.9 63.3 60/70
7.5/10 36.1 41.7 69.3 76.3 70/80
11.3/15 54.1 62.5 91.8 102.3 100/110
42 208/230-1-60 197 253 16.3 112.3 1.7 4.1
-/- - - 26.1 26.1 40
3.8/5 18 20.8 48.7 52.5 50/60
5.6/7.2 27 31.3 59.9 65.3 60/70
7.5/10 36.1 41.7 71.3 78.3 80/80
11.3/15 54.1 62.5 93.8 104.3 100/110
48 208/230-1-60 197 253 18.3 108.0 1.7 6.0
-/- - - 30.6 30.6 45
3.8/5 18 20.8 53.1 56.6 60/60
5.6/7.2 27 31.3 64.3 69.7 70/70
7.5/10 36.1 41.7 75.7 82.7 80/90
11.3/15 54.1 62.5 98.2 108.7 100/110
15.0/20.0 72.1 83.3 120.7 134 125/150
60 208/230-1-60 197 253 26.2 144.2 1.9 7.6
-/- - - 42.3 42.3 60
3.8/5 18 20.8 64.8 68.3 70/70
5.6/7.2 27 31.3 76.0 81.4 80/90
7.5/10 36.1 41.7 87.4 94.4 90/100
11.3/15 54.1 62.5 109.9 120.4 110/125
15.0/20.0 72.1 83.3 132.4 146.4 150/150
*kW @ 208/240
** HACR Type Circuit Breaker
LEGEND
F L A --- F u l l L o a d A m p s
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
RLA --- Rated Load Amps
NOTES:
1. In compliance with NE C (Na tional E lectrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker.
2. Minimum wire size is based on 60_Ccopperwire.Ifotherthan60_C wire is used, or if length exceeds wire length in table, determine size from NEC.
*Heater capacity (kW) based on h ea ter vol tage of 208v & 240v. If power distribution voltage to unit var ies from rated heater voltage, heater kW will vary accord-
ingly.
PH4Z