Specs

17
PERFORMANCE DATA (CONT)
LEGEND
BF— Bypass Factor
d b --- D r y B u l b
edb— Entering Dry ---Bulb
Ewb Entering Wet--- Bulb
kW Total Unit Power Input
ldb— Leaving Dry ---Bulb
lwb Leaving Wet--- Bulb
SHC Sensible Heat Capacity (1000 Btuh)
TC Total Capacity ( 1000 Btuh) ( net)
*At 75_F (23.9_C) entering dry bulb (Tennessee Valley Authority [TVA] rating conditions); all other at 80_F ( 26.75_ C) entering dry bulb.
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator---fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
Sensible capacity
(Btuh)
1.10 x CFM
t
ldb =
t
edb
--
Wet--bulb temperature corresponding to enthalpy
air leaving evaporator coil (
h
lwb)
t
lwb =
total capacity (Btuh)
4.5xCFM
h
lwb =
h
ewb --
Where:
h
ewb = Enthal py of air entering evaporator coil
4. The S HC is based on 80_F (26.7_C) edb temperature of air en tering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x CFM) from SHC.
Above 80_F (26.7_C) edb, add (corr factor x CFM) to SHC.
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80) .
PH4Z