Specs

13
PERFORMANCE DATA (CONT)
COOLING CAPACITY
036
EVA PORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (24) 85 (29) 95 (35) 105 (41) 115 (46) 125 (52)
CFM EWB
Capacity
MBtuh
To t a l
Sys
kW
Capacity
MBtuh
To t a l
Sys
kW
Capacity
MBtuh
To t a l
Sys
kW
Capacity
MBtuh
To t a l
Sys
kW
Capacity
MBtuh
To t a l
Sys
kW
Capacity
MBtuh
To t a l
Sys
kW
To t a l Sens To t a l Sens To t a l Sens To t a l Sens To t a l Sens To t a l Sens
1050
57 (14) 35.93 35.93 2.36 33.75 33.75 2.70 31.52 31.52 3.08 29.19 29.19 3.52 26.69 26.69 4.03 23.44 23.44 4.55
62 (17) 37.16 32.72 2.36 34.64 31.84 2.70 32.05 30.86 3.08 29.38 29.75 3.52 26.74 26.74 4.03 23.49 23.49 4.55
63* (17) 37.80 26.59 2.36 35.24 25.75 2.70 32.57 24.84 3.08 29.78 23.85 3.52 26.72 22.69 4.03 22.54 20.97 4.53
67 (19) 40.63 27.40 2.36 38.07 26.70 2.70 35.38 25.86 3.09 32.52 24.93 3.54 29.45 23.92 4.05 25.85 22.65 4.64
72 (22) 43.93 21.95 2.37 41.38 21.32 2.72 38.64 20.59 3.12 35.74 19.79 3.57 32.68 18.87 4.08 29.43 17.90 4.66
1200
57 (14) 37.48 37.48 2.39 35.25 35.25 2.73 32.94 32.94 3.12 30.53 30.53 3.56 27.93 27.93 4.08 24.77 24.77 4.64
62 (17) 38.06 35.03 2.39 35.55 34.11 2.73 33.04 32.82 3.12 30.58 30.58 3.56 27.97 27.97 4.08 24.83 24.83 4.64
63* (17) 38.56 28.13 2.39 35.95 27.33 2.73 33.26 26.45 3.12 30.41 25.47 3.56 27.26 24.30 4.08 23.13 22.62 4.58
67 (19) 41.32 28.90 2.39 38.73 28.26 2.74 36.00 27.47 3.13 33.12 26.57 3.58 30.03 25.59 4.09 26.44 24.43 4.67
72 (22) 44.53 22.75 2.41 41.96 22.17 2.76 39.19 21.46 3.16 36.22 20.68 3.61 33.12 19.74 4.12 29.83 18.82 4.70
1350
57 (14) 38.67 38.67 2.42 36.40 36.40 2.76 34.04 34.04 3.15 31.58 31.58 3.60 28.94 28.94 4.12 25.94 25.94 4.71
62 (17) 38.83 36.99 2.42 36.44 36.44 2.76 34.09 34.09 3.15 31.62 31.62 3.60 28.98 28.98 4.12 25.98 25.98 4.71
63* (17) 39.12 29.53 2.42 36.50 28.79 2.77 33.77 27.94 3.16 30.89 26.97 3.60 27.73 25.85 4.11 23.68 24.16 4.64
67(19) 41.83 30.27 2.43 39.21 29.67 2.77 36.45 28.95 3.17 33.55 28.08 3.62 30.48 27.11 4.13 26.96 26.05 4.71
72 (22) 44.95 23.44 2.44 42.38 22.92 2.80 39.58 22.24 3.20 36.58 21.46 3.65 33.42 20.55 4.16 30.10 19.65 4.75
Seepage17forcoolingnotes.
HEATING CAPACITY
036
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES _F(°C)
-10 (-23) 0 (-18) 10 (-12) 20 (-7) 30 (-1) 40 (4) 50 (10) 60 (16)
EDB CFM
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Capacity
MBtuh
Tota l
Sys
kW
Tota l Integ Tota l Integ To tal Integ To t al Integ Tota l Integ To tal Integ To tal Integ Tota l Integ
65
(18)
1050 10.63 9.78 2.08 13.98 12.86 2.18 17.60 16.15 2.29 21.69 19.67 2.41 26.19 22.94 2.56 30.74 30.74 2.70 36.06 36.06 2.85 41.91 41.91 3.00
1200 10.83 9.96 2.09 14.19 13.05 2.19 17.87 16.40 2.30 22.40 20.31 2.42 26.47 23.19 2.54 31.10 31.10 2.66 36.49 36.49 2.79 42.00 42.00 2.93
1350 11.01 10.13 2.11 14.39 13.24 2.21 18.09 16.61 2.31 22.61 20.51 2.42 26.70 23.40 2.53 31.39 31.39 2.65 36.68 36.68 2.76 41.92 41.92 2.89
70
(21)
1050 10.08 9.27 2.15 13.46 12.38 2.26 17.08 15.67 2.38 21.12 19.15 2.51 25.84 22.64 2.67 30.33 30.33 2.82 35.56 35.56 2.99 41.41 41.41 3.14
1200 10.27 9.45 2.17 13.66 12.57 2.27 17.36 15.94 2.38 21.43 19.44 2.50 26.11 22.88 2.65 30.67 30.67 2.78 36.02 36.02 2.92 41.55 41.55 3.07
1350 10.45 9.61 2.19 13.86 12.75 2.29 17.59 16.14 2.39 21.70 19.68 2.50 26.35 23.09 2.64 30.96 30.96 2.77 36.27 36.27 2.89 41.52 41.52 3.02
75
(24)
1050 9.51 8.75 2.24 12.91 11.88 2.35 16.55 15.19 2.48 20.59 18.68 2.61 25.51 22.35 2.79 29.92 29.92 2.95 35.06 35.06 3.13 40.90 40.90 3.29
1200 9.70 8.92 2.26 13.14 12.09 2.37 16.82 15.44 2.48 20.89 18.95 2.60 25.78 22.59 2.76 30.26 30.26 2.91 35.52 35.52 3.06 41.07 41.07 3.21
1350 9.86 9.07 2.28 13.33 12.27 2.38 17.04 15.64 2.49 21.15 19.18 2.61 26.00 22.78 2.75 30.54 30.54 2.89 35.82 35.82 3.02 41.08 41.08 3.16
PH4Z