cooling operation down to 40F (4.4C). It’s high efficiency design ensures high performance with most duct systems. REFRIGERANT SYSTEM is designed to provide dependability. Liquid refrigerant filter driers are used to promote clean, unrestricted operation. Each unit leaves the factory with a full refrigerant charge and is fully run tested. Refrigerant service connections make checking operating pressure easier.
AHRI* CAPACITIES Cooling Capacities and Efficiencies UNIT SIZE NOMINAL TONS STANDARD CFM 024 030 036 042 048 060 2 2.5 3 3.5 4 5 800 1000 1200 1400 1600 1700 NET COOLING CAPACITY AT 95° F (35° C) (Btuh) 24,000 29,800 36,000 42,000 46,500 55,000 EER† SEER** 11.50 11.50 11.50 11.50 11.50 11.00 14.50 14.50 14.50 14.50 14.00 14.00 Heat Pump Heating Capacities and Efficiencies NET HEATING CAPACITY AT 47° F (8.3° C) (Btuh) 23,400 28,600 34,400 40,000 45,000 56,000 COP @ 47° F (8.
PHYSICAL DATA UNIT SIZE 024 030 036 042 048 060 NOMINAL CAPACITY (ton) 2 2.5 3 3.5 4 5 SHIPPING WEIGHT (lb) (kg) 312 142 333 151 334 152 388 177 407 185 475 215 9.10 4.13 7.70 3.49 11.5 5.22 COMPRESSOR TYPE SCROLL PH4Z REFRIGERANT R-410A REFRIGERANT QUANTITIY (lb) QUANTITY (kg) 7.00 3.18 OUTDOOR METERING DEVICE TXV TXV Piston ORIFICE ID (in.) (mm) ----- 0.049 1.245 0.057 1.448 0.059 1.499 ----- 0.070 1.778 OUTDOOR COIL ROWS...FINS/in. FACE AREA (sq. ft) 2...20 9.
OPTIONS AND ACCESSORIES DESCRIPTION Coil Options Compressor Start Kit Corporate Thermostats Crankcase Heater Electric Heaters Low Ambient Kit Time Guard II Refer to Price Pages for available accessories. Base unit with tin plated indoor coil hairpins Compressor Start Kit assists compressor start---up by providing additional starting torque. Thermostats provide control for the system heating and cooling functions. Crankcase Heater provides anti ---floodback protection for low ---load cooling applications.
PH4Z BASE UNIT DIMENSIONS—024--036 A14556 6
PH4Z BASE UNIT DIMENSIONS—042--048 A14557 7
PH4Z BASE UNIT DIMENSIONS—060 A150072 8
SELECTION PROCEDURE I. DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS Given: Required Cooling Capacity (TC . . . . . . . . . . . 28,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 20,500 Btuh Required Heating Capacity . . . . . . . . . . . . . . . 28,550 Btuh Outdoor Entering--Air Temperature . . . . . . . . 95F (35C) Outdoor--Air Winter Design Temperature . . 20F (--6.7C) Indoor--Air Winter Design Temperature . . . . . . . . . . . .70F (21.
A150088 10 BUILDING HEAT LOSS, UNIT INTEGRATED HEATING CAPACITY, MBTUH 0 -10 0 10 20 30 40 OUTDOOR TEMPERATURE, ºF 50 60 BASED ON INDOOR ENT. AIR AT 70 ºF AND AT RATED CFM 70 0.0 2.9 10 8.8 11.7 14.6 17.6 20.5 5.9 24 30 36 42 48 60 23.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) EWB 75 (24) 70 (21) 65 (18) EDB -10 (-23) 7.21 7.25 7.29 7.13 7.16 7.19 7.06 7.09 7.12 800 900 700 800 900 700 800 900 Total 6.55 6.52 6.50 6.61 6.58 6.56 6.70 6.67 6.64 Integ Capacity MBtuh 700 CFM INDOOR AIR HEATING CAPACITY 024 1.57 1.57 1.57 1.50 1.50 1.50 1.43 1.43 1.43 Total Sys kW 0 (-18) Total Sys kW 1.40 1.40 1.40 1.41 1.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67(19) 72 (22) EWB 75 70 65 EDB -10 (-23) 7.01 7.11 1125 6.90 875 1000 7.40 1125 7.19 875 7.30 7.67 1125 1000 7.58 7.47 Total 6.55 6.45 6.35 6.81 6.72 6.61 7.06 6.97 6.87 Integ Capacity MBtuh 1000 875 CFM INDOOR AIR HEATING CAPACITY 030 1.72 1.72 1.71 1.65 1.64 1.64 1.57 1.57 1.56 Total Sys kW 0 (-18) Total Sys kW 1.83 1.83 1.84 1.87 1.91 1.86 1.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67(19) 72 (22) EWB 75 (24) 70 (21) 65 (18) EDB 1050 1200 1350 1050 1200 1350 1050 1200 1350 CFM INDOOR AIR -10 (-23) Capacity MBtuh Total Integ 10.63 9.78 10.83 9.96 11.01 10.13 10.08 9.27 10.27 9.45 10.45 9.61 9.51 8.75 9.70 8.92 9.86 9.07 HEATING CAPACITY 036 2.08 2.09 2.11 2.15 2.17 2.19 2.24 2.26 2.28 Total Sys kW Total Sys kW 2.36 2.36 2.36 2.36 2.37 2.39 2.39 2.39 2.39 2.41 2.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) EWB 75 (24) 70 (21) 65 (18) EDB 1225 1400 1575 1225 1400 1575 1225 1400 1575 CFM INDOOR AIR -10 (-23) Capacity MBtuh Total Integ 12.34 11.36 12.54 11.54 12.71 11.69 11.85 10.90 12.06 11.09 12.24 11.26 11.26 10.36 11.48 10.56 11.67 10.74 HEATING CAPACITY 042 2.53 2.55 2.57 2.61 2.63 2.65 2.68 2.70 2.73 Total Sys kW Total Sys kW 2.64 2.64 2.65 2.67 2.69 2.68 2.69 2.69 2.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) EWB 75 (24) 70 (21) 65 (18) EDB 1400 1600 1800 1400 1600 1800 1400 1600 1800 CFM INDOOR AIR -10 (-23) Capacity MBtuh Total Integ 15.18 13.97 15.30 14.07 15.41 14.18 15.09 13.89 15.19 13.97 15.29 14.07 15.08 13.88 15.16 13.95 15.25 14.03 HEATING CAPACITY 048 2.94 2.96 2.99 3.06 3.08 3.11 3.20 3.22 3.24 Total Sys kW Total Sys kW 3.18 3.18 3.18 3.20 3.22 3.23 3.23 3.24 3.
57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) 57 (14) 62 (17) 63* (17) 67 (19) 72 (22) EWB 75 70 65 EDB 1500 1700 1850 1500 1700 1850 1500 1700 1850 CFM INDOOR AIR Total 20.53 20.57 20.61 20.52 20.57 20.62 20.49 20.55 20.60 Integ 18.88 18.92 18.96 18.88 18.92 18.97 18.85 18.91 18.96 -10 (-23) Capacity MBtuh 3.42 3.41 3.41 3.60 3.59 3.59 3.80 3.78 3.78 Total Sys kW Total 24.97 24.98 25.01 24.95 24.97 25.00 24.92 24.94 24.97 Integ 22.98 22.99 23.01 22.
= 1.10 x CFM Sensible capacity (Btuh) air leaving evaporator coil (hlwb) Wet--bulb temperature corresponding to enthalpy = tedb - hlwb total capacity (Btuh) = hewb -4.5 x CFM 4. The SHC is based on 80_F (26.7_C) edb temperature of air entering evaporator coil. Below 80_F (26.7_C) edb, subtract (corr factor x CFM) from SHC. Above 80_F (26.7_C) edb, add (corr factor x CFM) to SHC. Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
PERFORMANCE DATA (CONT) Filter Pressure Drop (IN. W.C.) FILTER SIZE in. (mm) 20X20X1 (508X508X25) 20X24X1 (508X610x25) 24X30X1 (610X762x25) 24X36X1 (610X914X25) CFM 1300 1400 500 600 700 800 900 1000 1100 1200 1500 1600 1700 1800 1900 2000 2100 2200 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — — — — — — — — — — — — — 0.08 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — — — — — — — — — — 0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.
Voltage Range MIN MAX Units Nominal V-PH-HZ 24 208/230-1-60 197 30 208/230-1-60 36 Compressor RLA LRA OFM FLA IFM FLA 253 10.3 61.6 0.9 2.8 197 253 13.5 72.5 0.9 2.8 208/230-1-60 197 253 14.7 75.0 1.7 4.1 42 208/230-1-60 197 253 16.3 112.3 1.7 4.1 48 208/230-1-60 197 253 18.3 108.0 1.7 6.0 60 208/230-1-60 197 253 26.2 144.2 1.9 7.6 Electrical Heat Nominal FLA kW* 208 240 -/3.8/5 18 20.8 5.6/7.2 27 31.3 7.5/10 36.1 41.7 -/3.8/5 18 20.8 5.6/7.2 27 31.3 7.
TYPICAL INSTALLATION INDOOR THERMOSTAT RETURN AIR FROM POWER SOURCE PH4Z TOP COVER POWER ENTRY COMPOSITE RUST-PROOF BASEPAN Power Wiring Control Wiring LOW VOLTAGE ENTRY DISCONNECT PER NEC (UNIT AND ELECTRIC HEATER) CONDENSATE DRAIN CONNECTION Condenser Airflow Evaporator Airflow A10135 20
PH4Z TYPICAL CONNECTION WIRING SCHEMATIC—208/230--1--60 A14563 21
PH4Z TYPICAL LADDER WIRING SCHEMATIC—208/230--1--60 A14564 22
TYPICAL WIRING SCHEMATIC (CONT) PH4Z Wires to be removed A14444 Accessory Electric Heater Wiring CONTROLS APPLICATION DATA Sequence of operation Condensate trap — A 2--in. (51 mm) condensate trap must be field supplied. When power is supplied to unit, the transformer (TRAN) is energized. Cooling Operation — With a call for cooling (O,Y,G), the reversing valve, contactor, and indoor fan are energized.
PH4Z GUIDE SPECIFICATIONS SMALL PACKAGED PRODUCT AIR--TO--AIR HEAT PUMP CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL (COOLING) PART I -- GENERAL SYSTEM DESCRIPTION Outdoor packaged, electrically controlled, air--to--air heat pump utilizing a scroll compressor for heating and cooling duty. Unit shall discharge supply air horizontally as shown on contract drawings. QUALITY ASSURANCE A. Unit shall be rated in accordance with AHRI Standards 210/240, and 270.
GUIDE SPECIFICATIONS (CONT) K. Grille 1. Louvered Grille: Louvered grille shall be standard on all units. L. Special Features Available 1. Coil Options: Shall include factory--installed optional tin--plated indoor coil. 2. Thermostat: To provide for two--stage heating and one--stage cooling in addition to manual or automatic changeover and indoor fan control. 3.