Install Manual

17
Wires to be removed
A14444
Fig. 15 -- Accessory Electric Heater Wiring
Table 5 W et Coil Air Delivery*
(Deduct 10 percent for 208 Volt Operation)
230 VOLT HORIZONTAL DISCHARGE
UNIT
SIZE
SPEED TAP AIR DELIVERY
2
EXTERNAL STA TIC PRESSURE (IN. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
1 SCFM 933 799 758 707 675 608 549 497 435 394
2 SCFM 1016 921 882 854 809 761 711 668 599 552
3 SCFM 1079 1041 1003 970 944 909 866 810 764 724
030
1 SCFM 1052 1018 984 943 914 879 833 795 732 678
2 SCFM 1141 1107 1069 1036 1006 974 932 899 856 784
3 SCFM 1246 1213 1181 1144 1108 1078 1043 1015 973 931
036
1 SCFM 1311 1253 1195 1136 1083 1023 958 895 818 729
2 SCFM 1413 1364 1313 1256 1203 1148 1084 1022 969 882
3 SCFM 1571 1525 1473 1423 1364 1313 1261 1210 1156 1090
042
1 SCFM 1499 1434 1394 1349 1307 1273 1232 1169 1108 1038
2 SCFM 1568 1532 1497 1459 1407 1381 1346 1304 1252 1185
3 SCFM 1635 1593 1560 1523 1484 1439 1406 1369 1335 1264
048
1 SCFM 1657 1625 1590 1554 1517 1486 1448 1417 1381 1340
2 SCFM 1707 1673 1644 1614 1586 1549 1515 1479 1449 1407
3 SCFM 1931 1900 1870 1840 1809 1778 1749 1714 1683 1646
060
1 SCFM 1774 1746 1717 1678 1639 1590 1538 1492 1461 1418
2 SCFM 1857 1820 1784 1752 1720 1671 1625 1579 1532 1509
3 SCFM 2183 2144 2115 2079 2049 2018 1986 1933 1859 1733
*Air delivery val ues are based on operating vol tage of 230v, wet coil, without filter or electric heater. Deduct filter an d electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occuratair-
flows below this point.
2. Standard Cubic Feet per Minute
PH4Z