Specs
Table Of Contents
5
OUTDOOR UNIT CONNECTED TO FACTORY APPROVED INDOOR UNIT
Check piston size shipped with indoor unit to see if it matches required indoor piston size. If it does not match, replace indoor piston with
correct piston size in table below .
OUTDOOR UNIT
TONNAGE
FAN COIL
PISTON SIZE BY OUTDOOR MODEL
PA14NC
018
FB4CNF018L 49
FFMANP018 50
FPMAN*018 50
024
FB4CNF024L 55
FFMANP024 57
FPMAN*024 56
030
FB4CNF030L 61
FPMAN*030 67
FFMANP030 65
036
FB4CNF036L 67
FFMANP036 72
FPMAN*036 70
042 FB4CNF048L 76
048 FB4CNF048L 80
NOTE: Pistons are shipped with select outdoor units in the accessory bag and are only qualified for piston fan coils. Example fan coils with piston: FB4CNF and FPMAN (1.5 through 4 ton).
ACCESSORIES
Accessory Kit
Number
Description 018 024 030 036 042 048 060
HC32GE234 MOTOR,FAN X
HC34GE239 MOTOR,FAN X X
HC38GE219 MOTOR,FAN X X
HC40GE226 MOTOR,FAN X X
HH07AT212 BASE,THERM/SUB X X X X X X X
KAACF1001MED FILTER KIT X X X X
KAACF1101LRG FILTER KIT X X X
KAACH1201AAA CRKC HTR X X X
KAACH1401AAA CRKC HTR X X X X
KAACS0201PTC KIT PTC X X X X X X X
KAAFT0101AAA FREEZE THERMOSTAT X X X X X X X
KAAHI0501PUR HIGH PRESSURE SWITCH X X X X X X X
KAALP0401PUR LOW PRESSURE SWITCH X X X X X X X
KAALS0201LLS LIQUID LINE SOL VALVE X X X X X X X
KAATD0101TDR TIME DELAY RELAY X X X X X X X
KAAWS0101AAA WI NTER START KIT X X X X X X X
KSACY0101AAA CYCLE PROTECTOR X X X X X X X
KSAHS1501AAA HARD START KIT X X X X X X X
KSALA0301410 LOW AMBIENT PSW X X X X X X X
KSALA0601AAA MOTORMASTER 230V X X X X X X X
KSASH0601COP SOUND BLKT X X
KSASH1801COP SOUND BLKT X X X
KSASH2101COP SOUND BLKT X
KSATX0201PUR TXV KIT X X X
KSATX0301PUR TXV KIT X X
KSATX0401PUR TXV KIT X
KSATX0501PUR TXV KIT X
KSBTX0201PUR TXV KIT X X X
KSBTX0301PUR TXV KIT X X
KSBTX0401PUR TXV KIT X
TSTATXXSEN01 SENSOR X X X X X X X
X = Accessory
ACCESSORY USAGE GUIDELINE
ACCESSORY
REQUIRED FOR LOW---AMBIENT
COOLING APPLIC ATIONS
(Below 55F/12.8_C)
REQUIRED FOR LONG LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
Ball Bearing Fan Motor Ye s{ No No
Compressor Start Assist Capacitor and Relay Ye s Ye s No
Crankcase Heater Ye s Ye s No
Evaporator Freeze Thermostat Ye s No No
H a r d S h u t --- O f f T X V Ye s Ye s Ye s
Liquid Line Solenoid Valve No No No
Motor Master
Control or
Low ---ambient Pressure Switch
Ye s No No
Support Feet Recommended No Recommended
Winter Start Control Ye s No No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline Application Guideline.
{ Required for Low--- Ambient Controller (full modulation feature) MotorMasterr Control.