Specs

15
DETAILED COOLING CAPACITIES# CONTINUED
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERATURES ° F C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F(°C)
Capacity MBtuh
Tot a l
System
KW**
Capacity MBtuh
Tot a l
System
KW**
Capacity MBtuh
Tot a l
System
KW**
Capacity MBtuh
Tot a l
System
KW**
Capacity MBtuh
Tot a l
System
KW**
Capacity MBtuh
Tot a l
System
KW**
PA14NC060****A Outdoor Section With CAP**6024AL* Indoor Section
1750
72 (22.2) 68.41 35.82 4.01 65.35 34.67 4.39 62.15 33.49 4.86 58.70 32.23 5.39 55.01 30.89 5.96 50.87 29.41 6.55
67 (19.4) 62.24 44.04 4.01 59.41 42.88 4.38 56.50 41.69 4.83 53.38 40.43 5.35 50.00 39.08 5.91 46.23 37.59 6.49
63 (17.2)†† 57.78 42.37 4.02 55.13 41.19 4.37 52.41 39.99 4.81 49.54 38.75 5.32 46.39 37.40 5.87 42.89 35.91 6.45
62 (16.7) 56.92 52.17 4.02 54.40 50.96 4.37 51.84 49.69 4.81 49.16 49.16 5.32 46.64 46.64 5.88 43.73 43.73 6.46
57 (13.9) 55.64 55.64 4.02 53.56 53.56 4.37 51.43 51.43 4.81 49.13 49.13 5.32 46.56 46.56 5.88 43.68 43.68 6.46
2000
72 (22.2) 69.54 37.55 4.10 66.36 36.39 4.49 63.04 35.18 4.96 59.50 33.91 5.49 55.63 32.53 6.06 51.36 31.03 6.66
67 (19.4) 63.30 46.83 4.11 60.35 45.64 4.47 57.34 44.44 4.93 54.11 43.16 5.45 50.61 41.77 6.01 46.74 40.24 6.60
63 (17.2)†† 58.79 44.95 4.11 56.04 43.76 4.47 53.23 42.55 4.91 50.24 41.27 5.42 47.00 39.89 5.98 43.39 38.33 6.56
62 (16.7) 58.25 55.83 4.11 55.72 55.33 4.47 53.37 53.37 4.91 50.91 50.91 5.43 48.16 48.16 5.99 45.09 45.09 6.58
57 (13.9) 57.80 57.80 4.11 55.59 55.59 4.47 53.30 53.30 4.91 50.84 50.84 5.43 48.11 48.11 5.99 45.03 45.03 6.58
2250
72 (22.2) 70.37 39.17 4.20 67.10 37.99 4.59 63.67 36.77 5.06 60.02 35.48 5.59 56.04 34.08 6.17 51.66 32.55 6.76
67 (19.4) 64.08 49.47 4.20 61.08 48.28 4.57 57.95 47.04 5.03 54.64 45.73 5.55 51.07 44.31 6.12 47.12 42.69 6.70
63 (17.2)†† 59.56 47.41 4.20 56.73 46.20 4.56 53.82 44.95 5.01 50.77 43.65 5.52 47.44 42.21 6.08 43.78 40.57 6.66
62 (16.7) 59.69 59.69 4.20 57.32 57.32 4.56 54.90 54.90 5.02 52.28 52.28 5.53 49.41 49.41 6.10 46.17 46.17 6.69
57 (13.9) 59.58 59.58 4.20 57.25 57.25 4.56 54.83 54.83 5.02 52.23 52.23 5.53 49.35 49.35 6.10 46.12 46.12 6.69
{ Total and sensible capacities are net capacities. Blo wer motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air f or each degree below 80_F(27_C), or add 835 B tuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on i ndoor and outdoor unit at the same elevation per AHRI standard 210/ 240---2008. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
** System kw is total of indoor and o utdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/ 6 3_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls be tween the publi shed data, interpolatio n may be performed. Extrapola ti on i s not an acceptabl e practice.
EWB Entering Wet Bulb