Installation Manual
BEFORE PERFORMING EVACUATION
Check to make sure that both high-pressure 
and low-pressure pipes between the indoor 
and outdoor units are connected properly in 
accordance with the Refrigerant Piping 
Connection section of this manual.
Check to make sure all wiring is 
connected properly.
Preparations and Precautions
Compound gauge
-76cmHg
pressure
valve
High
pressure 
valve
Charge hose
Charge hose
Vacuum
pump
Pressure gauge
e
Fig. 6.1
MC MC
Evacuation Instructions
Before using the manifold gauge and vacuum pump, 
read their operation manuals to familiarize yourself 
with how to use them properly.
Air and foreign matter in the refrigerant circuit can 
cause abnormal rises in pressure, which can 
gauge to evacuate the refrigerant circuit, removing 
any non-condensable gas and moisture from the 
system. Evacuation should be performed upon initial 
installation and when unit is relocated.
1.  Connect the charge hose of the manifold gauge 
to service port on the outdoor unit’s low pressure 
valve.
2. Connect another charge hose from the manifold 
gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold gauge. 
Keep the High Pressure side closed.
4.  Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the 
Compound Meter reads -76 cmHG (-105 Pa).
6. Close the Low Pressure side of the manifold gauge, 
7.  Wait for 5 minutes, then check that there has been no 
change in system pressure.
8.  If there is a change in system pressure, refer to the Gas 
Leak Checks section for information on how to check for 
leaks. If there is no change in system pressure, unscrew 
the cap from the packed valve (high pressure valve).
9.  Insert a hexagon wrench into the packed valve (high 
pressure valve) and open the valve by turning the wrench 
in a 1/4 counter-clockwise turn. Listen for gas to exit the 
system, then close the valve after 5 
seconds.
10.  Watch the Pressure Gauge for one minute to make 
sure that there is no change in pressure. The Pressure 
Gauge should read slightly higher than atmospheric 
pressure.
11.  Remove the charge hose from the service port.
12. 
pressure (MAIN) and low pressure (MAIN) valves.
13.  Tighten valve caps on all three valves (service port, 
high pressure, low pressure) by hand. You may tighten it 
further using a torque wrench if needed.
6
Air Evacuation
Page 31
OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal
wrench until it hits against the stopper. DO 
NOT try to force the valve to open further.
mrcool.com










