Installation Guide
76
Symptom Possible Cause Action
Heating equipment is
running in the cool
mode.
Heating equipment is not a
heat pump but System Type
(Installer Setup Number
0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the
installed heating and/or cooling
equipment.
Heating equipment
does not turn off and
heat temperature
setting is set below
room temperature
Heating equipment is not a
heat pump but System Type
(Installer Setup Number
0170) is set to Heat Pump.
Set System Type (Installer Setup
Number 0170) to match the
installed heating and/or cooling
equipment.