Installation Guide

507277-03CPage 10 of 53 mrcool.com
Figure 11. Setting Equipment
FRONTVIEW SIDEVIEW
AIR FLOW
AIR FLOW
1/2"
max.
AIR FLOW
SIDEVIEW
Unit must be level sideto−side. Unit may be positioned
from level to 1/2"towardthe frontto aid in draining.
Figure 12.
WARNING
Top
Bottom
Left Side Right Side
Top 0
*Front 0
Back 0
Sides 0
Vent 0
Floor NC
*Frontclearancein alcove installationmustbe 24 in. (610mm).
Maintain a minimumof 24 in. (610mm) for frontserviceaccess.
Allow proper clearances to accommodate condensate trap.
The furnace may be installed on a combustible wood
oorifan optional
additive base is install
Figure 13.
Clearances
0
*Front 0
Back 0
Sides 0†
0
NC‡
See Figure 14
Table 1.
Cabinet Width
Front to Rear Side to Side
in. mm in. mm
19-3/4 502 16-5/8 422
19-3/4 502 20-1/8 511