Owners Manual
Page 10mrcool.com
No-Vac
®
 Quick Connect
®
 Line Set* Installation
INSTRUCTIONS FOR USE WITH
 NO-VAC™ QUICK CONNECT® LINE SET* 
SOLD SEPARATELY
37 ft/lb
37 ft/lb
52 ft/lb
52 ft/lb
M1
F1
M1 F1
M2
F2
M2 F2
*1
*1
*2
*2
3/8”
3/8”
3/4”
3/4”
Complete unit replacement 
using the No-Vac® Quick Connect® lines 
Air Handler
Open the stop/cuto 
valves only after 
connecting the 
refrigerant lines
A-coil Precharged 
with R-410A Refrigerant 
Connect using precharged 
line set with quick connect 
ttings in length 15, 25, 35, 50 feet
MRCOOL Universal Series 
DC Inverter
KINK RESISTANT, PRECHARGED, SIMPLE SECURE QUICK CONNECT, 100% CONNECTION GUARANTEE
www.mrcool.com
v10-25-2021
IMPORTANT
When running the Line Set 
through the knockout hole of 
the condenser, it may be 
necessary to slightly trim the 
line set insulation so it feeds 
through the hole freely. 
Otherwise, it may be difficult 
to connect it to the condenser. 
Once the installation is 
complete, pack the hole with 
neoprene to prevent small 
animals and insects from 
entering the condenser.
*
 :
1.
Take out matching male connectors M1 and M2.
2.
DC INVERTER 
and ensure the threads are clean and complete.
3.
the M1 connector to the .
the M2 connector to the .
4.
Repeat AIR HANDLER LINE SET.
5.
Unroll and route the LINE SET between the AIR HANDLER and the DC INVERTER. Bend the line 
6.
threads are clean and complete.
7.
the LINE SET F1 valve to the M1 Connector 
 . the LINE SET F2 valve to the M2 Connector 
 .
8. Repeat AIR HANDLER LINE SET.
9.
At the the at the and open the 
If 
grease or other close the valve and that steps 3 and 7 
were done properly. Otherwise
 it indicates there is a 
close the valve and that steps 3 and 7 were done 
10. the 
valve’s and the 
M1M2 and F1F2to help 
NOTE ON WRENCHES
The wrench sizes needed for tightening the 
No-Vac
®
 Quick Connect
®
 Line Set are listed 
below. However, based on the availability of the 
wrench sizes needed, it is recommended to use 
two large crescent (adjustable-type) wrenches. 
Using one to hold the valve while using the 
other wrench to tighten the line set connector. 
IMPORTANT
The stop/cutoff valves on the unit must 
be opened AFTER connecting the lines 
and BEFORE turning on the unit. 
Otherwise, operation can cause leakage 
and/or damage to the unit. 
Piping Size
(Stamped on piping)
Allen/Hex Wrench Sizes Needed
 To Open Stop/Cutoff Valves
Wrench Size Required
Standard Metric
Allen Wrench Size 
1”3/8”
3/8”
25 mm
1-3/8”3/4”
3/4”
35 mm
5 mm
8 mm
Piping/Valve Size
(Stamped on piping)
Or 2x large crescent (adjustable-type) 
wrenches
*Pat. https://mrcool.com/mrcool-patents/
ⱡFailure to follow the instrucons provided could result in severe harm to you, this product, or other property. 
The manufacturer, distributor, and seller are not responsible for any harm resulng from the failure to follow 
instrucons and the failure to follow these instrucons will void any and all warranes express or implied.