Unit Installation - OPTION 1: Conventional Weld / Flare Line Set
Conventional Line Set Installation
Specification of Connection Pipe
Piping Preparation
1. 
 WELD Type Complete Unit Replacement
All cut ends are to be round, burr free, and cleaned. Failure to follow this 
practice increases the chances for refrigerant leakage. Line set size matches 
service valve connection. DO NOT crimp service valve connector when pipe is 
smaller than connector. See diagram below.
2.  Screw Connection
Copper Piping 
Oil Applied (to reduce 
friction with the flare nut)
Oil Applied (improves 
air-tight seal)
Fig. 2.5
Fig. 2.4 
Fig. 2.3 
Torque Wrench
Spanner
Piping Union
Flare Nut 
Model
External diameter (inch)
Vapor pipe Liquid pipe
3/4 3/8
Pipe diameter (inch)
Tightening torque (N·m)
1/4
15-30 
3/8
35-40 
1/2
45-50 
5/8
60-65 
3/4
70-75 
7/8
80-85 
MDUI18048 / MDUI18060 
Purge with
Nitrogen
Must open stop valves 
after pulling vacuum 
and before powering
on unit
Weld joint 
Weld joint 
Air Handler
MRCOOL Universal® Series
DC Inverter
Open stop valves with allen 
wrench only after nishing 
lineset connections and before 
powering on the unit
Must install lter 
drier bi ow with this 
installation type
Must Purge with Nitrogen 
before brazing joints
Must Purge with 
Nitrogen before 
brazing joints