Use and Care Manual
Table Of Contents
- Foreword
 - Safety Notice
 - CONTENTS
 - Safety Notice on Maintenance
 - Safety Notice on Operation
 - 1 Product Introduction
 - NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
 - 2 Control
 - 3 Troubleshooting
- 3.1 Wiring Diagrams
 - 3.2 PCB Layout
 - 3.3 Error Code
 - 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
 - 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
 - 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
 - 3.4.4 “F2” Condenser Temperature Sensor Error
 - 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
 - 3.4.6 “F4” Discharge Temperature Sensor Error
 - 3.4.7 “F6” ODU Tube Temperature Sensor Error
 - 3.4.8“EE” ODU Memory Chip Error
 - 3.4.9 “H4” Overload
 - 3.4.10 “H5” IPM Protection
 - 3.4.11 “H6” DC Fan Error
 - 3.4.12 “H7” Driver Out-of-Step Protection
 - 3.4.13 “HC” PFC Protection
 - 3.4.14 “Lc” Startup Failure
 - 3.4.15 “P0” Driver Reset Protection
 - 3.4.16 “P5” Over-Current Protection
 - 3.4.17 “P6” Master Control and Driver Communication Error
 - 3.4.18 “P7” Driver Module Sensor Error
 - 3.4.19 “P8” Driver Module High Temperature Protection
 - 3.4.20 “PA” AC Current Protection
 - 3.4.21 “Pc” Driver Current Error
 - 3.4.22 “PL” Bus Low-Voltage Protection
 - 3.4.23 “PH” Bus High-Voltage Protection
 - 3.4.24 “PU” Charge Loop Error
 - 3.4.25 “ee” Drive Memory Chip Error
 
 - 3.5 Failures Not Caused by Errors
 
 - 4 Maintenance
 - Appendices
 - 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
 - 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
 - 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
 
 - 2 Temperature/Pressure List of Refrigerant
 - 3 Operation Tools
 
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT 
60 
For the removal of gas-liquid separator, please refer to the section: Removal of Major Components. 
Step 10: Check the system for leaks 
(1) First of all, check each welding point. Check whether the welding points are smooth and whether there is
any obvious welding hole or other abnormal condition.
(2) Next, fill high-pressure nitrogen into the system for leak detection. If it is only the outdoor unit that needs
to be repaired and the indoor unit is confirmed normal, then it’s OK to charge high-pressure nitrogen into
the outdoor unit only. Fill in the nitrogen simultaneously from the high pressure side and low pressure
side.  We  recommend  charging  the  nitrogen  from  the  big  and  small  valves  at  the  same  time.  The
pressure of  nitrogen should  be  above  20kgf.  Then  use  soapy  water  to  check  for  leaks.  Check  the
welding points particularly.
(3) Finally, retain the pressure of the system. Fill high-pressure nitrogen into the system and maintain the
pressure above 25kgf. Close the big and small valves and keep the pressure of indoor and outdoor units
for more than 12h. If the pressure remains unchanged, then start vacuum pumping; otherwise, check the
system for leaks again.
Temperature should  be  considered  when  judging  the  pressure  change.  If  temperature  changes by  1℃, 
pressure will change by 0.01MPa or so. 
For example, if temperature is 30℃ when nitrogen of 2.5MPa is charged, and temperature changes to 25℃ 
after 12h, we consider that the system is qualified if the pressure is found at 2.43MPa or above. 
Step 11: Evacuate the system and charge refrigerant 
Please refer to the section of maintenance: vacuum pumping and refrigerant charging. 
Step 12: Connect electric components 
Connect cables, compressor wires and the electric heating belt according to the signs marked before and 
the wiring diagram on the cover of the electric box. 
4.4.3 How to replace the drive module of compressor 
Step 1: First, make sure that power is cut off. Set the universal meter at the AC voltage and measure the 
voltage between L1, L2, L3, and N. If each time the voltage is 0V (Errors may occur to the universal meter, 
sometimes the voltage may not be 0V), proceed with the next step and put a sign on the power switch that reads 
“Under maintenance, don’t switch on”. 
Step  2:  Measure  the  voltage  between  DC  bus  P and  N  on  the  drive  board  of  the  compressor.  Set  the 
universal meter at the DC voltage and measure the voltage between P and N as shown below. If the voltage is 










