Use and Care Manual
Table Of Contents
- Foreword
 - Safety Notice
 - CONTENTS
 - Safety Notice on Maintenance
 - Safety Notice on Operation
 - 1 Product Introduction
 - NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
 - 2 Control
 - 3 Troubleshooting
- 3.1 Wiring Diagrams
 - 3.2 PCB Layout
 - 3.3 Error Code
 - 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
 - 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
 - 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
 - 3.4.4 “F2” Condenser Temperature Sensor Error
 - 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
 - 3.4.6 “F4” Discharge Temperature Sensor Error
 - 3.4.7 “F6” ODU Tube Temperature Sensor Error
 - 3.4.8“EE” ODU Memory Chip Error
 - 3.4.9 “H4” Overload
 - 3.4.10 “H5” IPM Protection
 - 3.4.11 “H6” DC Fan Error
 - 3.4.12 “H7” Driver Out-of-Step Protection
 - 3.4.13 “HC” PFC Protection
 - 3.4.14 “Lc” Startup Failure
 - 3.4.15 “P0” Driver Reset Protection
 - 3.4.16 “P5” Over-Current Protection
 - 3.4.17 “P6” Master Control and Driver Communication Error
 - 3.4.18 “P7” Driver Module Sensor Error
 - 3.4.19 “P8” Driver Module High Temperature Protection
 - 3.4.20 “PA” AC Current Protection
 - 3.4.21 “Pc” Driver Current Error
 - 3.4.22 “PL” Bus Low-Voltage Protection
 - 3.4.23 “PH” Bus High-Voltage Protection
 - 3.4.24 “PU” Charge Loop Error
 - 3.4.25 “ee” Drive Memory Chip Error
 
 - 3.5 Failures Not Caused by Errors
 
 - 4 Maintenance
 - Appendices
 - 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
 - 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
 - 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
 
 - 2 Temperature/Pressure List of Refrigerant
 - 3 Operation Tools
 
MRCOOL  DC INVERTER COOLING ONLY CONDENSING UNIT 
45 
Troubleshooting
:
PC Current detection
(or current sensor)
circuit error
Replace the drive
board.
3.4.22 “PL” Bus Low-Voltage Protection 
Error display:
 ODU mainboard LED displayer 
Error judgment condition and method: 
When compressor is running and there is no other malfunction, if busbar voltage is lower than the set value 
for low voltage protection, then it can be judged that bus low-voltage protection occurs. System will shut down for 
protection. 
Possible reason: 
■Voltage of power grid is abnormal.
■Drive board busbar voltage sampling circuit element is damaged or drive board busbar voltage sampling AD
terminal is abnormal. 
Troubleshooting
:
PL Bus low-voltage protection
Grid voltage is normal or not ?
Normal
protection
Replace the dr ive
board .
YES
NO