Use and Care Manual
Table Of Contents
- Foreword
 - Safety Notice
 - CONTENTS
 - Safety Notice on Maintenance
 - Safety Notice on Operation
 - 1 Product Introduction
 - NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
 - 2 Control
 - 3 Troubleshooting
- 3.1 Wiring Diagrams
 - 3.2 PCB Layout
 - 3.3 Error Code
 - 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
 - 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
 - 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
 - 3.4.4 “F2” Condenser Temperature Sensor Error
 - 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
 - 3.4.6 “F4” Discharge Temperature Sensor Error
 - 3.4.7 “F6” ODU Tube Temperature Sensor Error
 - 3.4.8“EE” ODU Memory Chip Error
 - 3.4.9 “H4” Overload
 - 3.4.10 “H5” IPM Protection
 - 3.4.11 “H6” DC Fan Error
 - 3.4.12 “H7” Driver Out-of-Step Protection
 - 3.4.13 “HC” PFC Protection
 - 3.4.14 “Lc” Startup Failure
 - 3.4.15 “P0” Driver Reset Protection
 - 3.4.16 “P5” Over-Current Protection
 - 3.4.17 “P6” Master Control and Driver Communication Error
 - 3.4.18 “P7” Driver Module Sensor Error
 - 3.4.19 “P8” Driver Module High Temperature Protection
 - 3.4.20 “PA” AC Current Protection
 - 3.4.21 “Pc” Driver Current Error
 - 3.4.22 “PL” Bus Low-Voltage Protection
 - 3.4.23 “PH” Bus High-Voltage Protection
 - 3.4.24 “PU” Charge Loop Error
 - 3.4.25 “ee” Drive Memory Chip Error
 
 - 3.5 Failures Not Caused by Errors
 
 - 4 Maintenance
 - Appendices
 - 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
 - 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
 - 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
 
 - 2 Temperature/Pressure List of Refrigerant
 - 3 Operation Tools
 
MRCOOL  DC INVERTER COOLING ONLY CONDENSING UNIT 
41 
■Drive  board  current  sampling  circuit  element  is  damaged  or  drive  chip  current  sampling  AD  terminal  is
abnormal. 
■Compressor is damaged.
Troubleshooting
:
3.4.17 “P6” Master Control and Driver Communication Error 
Error display:
 ODU mainboard LED displayer 
Error judgment condition and method: 
If there is no other malfunction and the communication between master control and driver is cut off for 30s, 
then it can be judged that the communication between master control and driver is faulted. System will shut down 
for protection.   