Use and Care Manual
Table Of Contents
- Foreword
 - Safety Notice
 - CONTENTS
 - Safety Notice on Maintenance
 - Safety Notice on Operation
 - 1 Product Introduction
 - NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
 - 2 Control
 - 3 Troubleshooting
- 3.1 Wiring Diagrams
 - 3.2 PCB Layout
 - 3.3 Error Code
 - 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
 - 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
 - 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
 - 3.4.4 “F2” Condenser Temperature Sensor Error
 - 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
 - 3.4.6 “F4” Discharge Temperature Sensor Error
 - 3.4.7 “F6” ODU Tube Temperature Sensor Error
 - 3.4.8“EE” ODU Memory Chip Error
 - 3.4.9 “H4” Overload
 - 3.4.10 “H5” IPM Protection
 - 3.4.11 “H6” DC Fan Error
 - 3.4.12 “H7” Driver Out-of-Step Protection
 - 3.4.13 “HC” PFC Protection
 - 3.4.14 “Lc” Startup Failure
 - 3.4.15 “P0” Driver Reset Protection
 - 3.4.16 “P5” Over-Current Protection
 - 3.4.17 “P6” Master Control and Driver Communication Error
 - 3.4.18 “P7” Driver Module Sensor Error
 - 3.4.19 “P8” Driver Module High Temperature Protection
 - 3.4.20 “PA” AC Current Protection
 - 3.4.21 “Pc” Driver Current Error
 - 3.4.22 “PL” Bus Low-Voltage Protection
 - 3.4.23 “PH” Bus High-Voltage Protection
 - 3.4.24 “PU” Charge Loop Error
 - 3.4.25 “ee” Drive Memory Chip Error
 
 - 3.5 Failures Not Caused by Errors
 
 - 4 Maintenance
 - Appendices
 - 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
 - 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
 - 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
 
 - 2 Temperature/Pressure List of Refrigerant
 - 3 Operation Tools
 
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT 
34 
Troubleshooting
:
Outdoor heat exchanger is blocked
Indoor heat exchanger is blocked.
Ambient temperature is out of the
operation range
H
4 Overload
Too much charging quantity.
Error still exist?
Remove the obstacle
Remove the obstacle
Normal protection. No
need to handle it.
Release a proper amount
of refrigerant
Replace the drive board
Replace the compressor
YES
YES
YES
YES
YES
NO
NO
NO
NO
3.4.10 “H5” IPM Protection 
Error display:
 ODU mainboard LED displayer
Error judgment condition and method: 
When power is connected and drive chip received IPM lead F0 that is of low level, then it is IPM module 
malfunction. System will shut down for protection. 
Possible reason: 
■Compressor 3-phase wire connection is lack of phase or phase-reversed.
■System is overloaded and compressor current is too large.
■Drive board IPM module is damaged.