Use and Care Manual

Table Of Contents
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
23
There are LED indicators on the main board of the indoor unit, which are used to display the operating status
and malfunction information of the unit.
LED indicator
Color
Function
Power Indicator
Red
Indoor unit main board is powered on, Power Indicator is on.
Running Indicator
Green
After detecting the indoor fan turn-on signal, the running indicator
light is on, when detecting the indoor fan turning-off signal, the
running indicator light is off. When detecting a system failure, the
running indicator light flashes.
Different running indicator flashing light means different system failure.
malfunction
Running Indicator status
Remark
Indoor Jumper cap failure
Light out 3S then flash once
Flash means light on 0.5S then light out 0.5S
Indoor fan failure
Light out 3S then flash twice
Indoor tube temperature
sensor failure
Light out 3S then flash four
times
3.4 Troubleshooting
3.4.1 “E1” Compressor High Pressure Protection
Error display: ODU mainboard LED displayer
Error judgment condition and method:
It is judged through the action of high pressure switch. If the high pressure switch is cut off, it is judged that
high pressure is too high and the system stops operation for protection.
Possible reason
■Cut-off valve of ODU is not fully opened;
■High pressure switch is abnormal;
■Outdoor or indoor fan is not working properly;
■Ambient temperature is too high;
■Refrigerant charging amount is too much;
■System pipeline is blocked