Use and Care Manual
Table Of Contents
- Foreword
- Safety Notice
- CONTENTS
- Safety Notice on Maintenance
- Safety Notice on Operation
- 1 Product Introduction
- NOTE: 1 Ton =12000Btu/h = 3.517kW 1.2 Electrical Parameters
- 2 Control
- 3 Troubleshooting
- 3.1 Wiring Diagrams
- 3.2 PCB Layout
- 3.3 Error Code
- 3.4 Troubleshooting
- 3.4.1 “E1” Compressor High Pressure Protection
- 3.4.2 “E3” Compressor Low-pressure Protection, Refrigerant Shortage Protection, Refrigerant Recovery Mode
- 3.4.3 “E4” Compressor Air Discharge High-temperature Protection
- 3.4.4 “F2” Condenser Temperature Sensor Error
- 3.4.5 “F3” Outdoor Ambient Temperature Sensor Error
- 3.4.6 “F4” Discharge Temperature Sensor Error
- 3.4.7 “F6” ODU Tube Temperature Sensor Error
- 3.4.8“EE” ODU Memory Chip Error
- 3.4.9 “H4” Overload
- 3.4.10 “H5” IPM Protection
- 3.4.11 “H6” DC Fan Error
- 3.4.12 “H7” Driver Out-of-Step Protection
- 3.4.13 “HC” PFC Protection
- 3.4.14 “Lc” Startup Failure
- 3.4.15 “P0” Driver Reset Protection
- 3.4.16 “P5” Over-Current Protection
- 3.4.17 “P6” Master Control and Driver Communication Error
- 3.4.18 “P7” Driver Module Sensor Error
- 3.4.19 “P8” Driver Module High Temperature Protection
- 3.4.20 “PA” AC Current Protection
- 3.4.21 “Pc” Driver Current Error
- 3.4.22 “PL” Bus Low-Voltage Protection
- 3.4.23 “PH” Bus High-Voltage Protection
- 3.4.24 “PU” Charge Loop Error
- 3.4.25 “ee” Drive Memory Chip Error
- 3.5 Failures Not Caused by Errors
- 4 Maintenance
- Appendices
- 1 Resistance/Temperature Lists of Temperature Sensors
- 1.1 Voltage List of 15 KΩ Temperature Sensors (including ODU temperature sensors)
- 1.2 Voltage List of 20 KΩ Pipeline Temperature Sensors (including temperature sensors for defroster, IDU and ODU pipes)
- 1.3 Voltage List of 50 KΩ Discharge Temperature Sensors (including discharge air temperature sensor)
- 2 Temperature/Pressure List of Refrigerant
- 3 Operation Tools
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
67
Removal of compressor/gas liquid separator
NOTE: Before removing the compressor/gas liquid separator, make sure there is no refrigerant in the pipeline and power is cut off.
Step
Picture
Work instruction
5. Install the new
compressor/gas liquid
separator onto the chassis.
Screws
Nuts
After replacing the
compressor/gas liquid
separator, tighten up the
base screw nuts.
6. Connect the welding
interfaces of
compressor/gas liquid
separator to the pipeline.
Pipe Welding
Interface
Weld the connection pipes
of compressor so as to
connect them to the
compressor.
NOTE: When replacing
the compressor, avoid
touching the nearby
pipeline and components.
7. Connect the compressor
wires.
Power
Terminals
Connect the compressor
wires to the wire terminals
on the top of compressor.
NOTE: When connecting
the wires, be sure to
match the colors with the
corresponding wire
terminals.