below 36V, proceed with the next step. In case that a universal meter is not available, disconnect power for 20min
and then continue with the next step.
Step 3: Remove all the wires on the drive board of the compressor.
Step 4: Remove the screws on the drive board of the compressor. The screws are located in the white circles
as shown above in the picture.
Step 5: Replace with a new compressor drive board. Before replacement, apply some silica gel on the IPM
module.
Step 6: Install the new compressor drive board. Fix the screws and connect the wires correctly.