Refer to the following table for the resistance between any two terminals:
Compressor model
UV Winding resistance
VW Winding resistance
WU Winding resistance
QXAS-D32zX090FA
1.02±7%Ω
1.02±7%Ω
1.02±7%Ω
QXAS-F428zX450L
0.54±7%Ω
0.54±7%Ω
0.54±7%Ω
Measure the earth resistance of each wiring terminal. The resistance should be above 10 megohm. If not, we
can judge that the compressor is faulted inside.
Step 3:
Check whether the IPM module is normal. Please refer to the IPM checking method in the section of
troubleshooting.
4.4.2.2 Replacement of compressor
Step 1: Preparation
(1) Prepare the components for replacement
When carrying the old and new compressors, do not place the compressors horizontally or upside down. The
angle of inclination should be within ±30°. Make sure the lubricant inside the compressors will not flow from the oil
balance mouth. The suction and exhaust openings of the compressors must be sealed. If a rubber seal is missing,
user adhesive tape to seal the opening. This is to prevent the compressor oil from contacting the air.
Make sure the rubber seals
of the suction and exhaust
openings of the compressor
are in good condition.