MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
50
4 Maintenance
4.1 System Diagram
4.2 Connection Pipe Vacuum Pumping
NOTICE
Make sure the outlet of vacuum pump is away from fire source and is well-ventilated.
Before vacuum pumping, make sure the unit cut-off valves are closed.
When vacuum pumping, both the liquid pipe and the gas pipe must be pumped.
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) meanwhile the gas and liquid valves should be kept closed in case of refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve assembly and start the vacuum pump.
Meanwhile, the switch at the high pressure side of the manifold valve assembly should be kept closed,
otherwise evacuation would fail.
(5) The evacuation duration depends on the unit’s capacity, generally.
Model
Time(min)
MDUCO18024036
30
MDUCO18048060
45