MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
34
Troubleshooting
Outdoor heat exchanger is blocked
Indoor heat exchanger is blocked.
Ambient temperature is out of the
operation range
H
4 Overload
Too much charging quantity.
Error still exist?
Remove the obstacle
Remove the obstacle
Normal protection. No
need to handle it.
Release a proper amount
of refrigerant
Replace the drive board
Replace the compressor
YES
YES
YES
YES
YES
NO
NO
NO
NO
3.4.10 “H5” IPM Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
When power is connected and drive chip received IPM lead F0 that is of low level, then it is IPM module
malfunction. System will shut down for protection.
Possible reason:
Compressor 3-phase wire connection is lack of phase or phase-reversed.
System is overloaded and compressor current is too large.
Drive board IPM module is damaged.