Use and Care Manual

Table Of Contents
MRCOOL DC INVERTER COOLING ONLY CONDENSING UNIT
7
2.2 Control Mode
2.2.1 Based Control
2.2.1.1 Compressor Control
When cooling mode is turned on, indoor fan will run for a while before the compressor starts. Under different
modes, the compressor can only be stopped after running for some time (special cases excluded). This is to
protect the compressor from frequent start or stop. Once the compressor is stopped, it must not be restarted right
away. Please wait for a few minutes.
2.2.1.2 Outdoor Fan Control
This series air conditioner has two types of outdoor units: one with a single fan and the other with double
fans. The outdoor fan can run at the highest level 10 and the lowest level 1. By controlling the speed of outdoor
fan, the unit can achieve cooling at low temperature. In fan mode, outdoor fan will not work.
2.2.2 Special Control
Oil Return Control
If the unit is running at low frequency for a long time, system will enable oil return control. This is to lead oil in
the pipeline back to the compressor so that the compressor will not be lack of oil. Generally, the oil return takes
about 5min. The compressor running frequency will be raised to the preset oil return frequency.
2.2.3 Protection Control
2.2.3.1 High Pressure Protection Control
System will enable high pressure protection control if the high pressure switch is detected open for
continuously a little time. Under high pressure protection, system will be shut down and display error code E1.
When high pressure protection occurs for the first time, system will restore operation if the high pressure
switch is detected to be reclosed for continuously a little time. When high pressure protection occurs for the
second time in a certain time period, system will not restore operation. You need to manually turn off the unit and
clear the error before restarting up the unit. (If high pressure protection occurs frequently, please send for
professional personnel to repair.)