MRCOOL 13SEER R410A Brochure
Description
Due to continuous product improvement, the specifications listed below are subject to change without notice, and the
values shown on product nameplates should be referred to as final.
Description
Note
Tested and rated in accordance with ARI Standard 210/240. Always check the S & R plate for electrical data on the
unit being installed. Unit is charged with enough refrigerant for a 25’ line set.
RLA - Rated Load Amps
LRA - Locked Rotor Amps
FLA - Full Load Amps
Product Specifications
MODEL MAC13018 MAC13024 MAC13030 MAC13036 MAC13042 MAC13048 MAC13060
Nominal Ratings
Nominal Cooling (Btu/h) 18000 24000 30000 36000 42000 48000 60000
Sound Pressure Level dB(A) 59 58 60 61 62 64 66
Compressor
RLA 7. 9 9.8 12.6 15.08 21.5 21 25
LRA 38 53 71 64 105 115 150
Condenser Fan Motor
Power output (HP) 1/6 1/6 1/6 1/4 1 /4 1/4 1/3
FLA 1.2 1.2 1.2 1.7 1.7 1.7 2.1
Refrigeration System
Refrigerant Line Size
Liquid valve size (inch) 3/8’’ 3/8’’ 3/8’’ 3/8’’ 3/8’’ 3/8’’ 1/2’’
Suction valve size (inch) 5/8’’ 5/8’’ 3/4’’ 3/4’’ 7/8’’ 7/8’’ 1-1/8’’
Valve Connection Type Brazed
Refrigerant Charge (oz) 52.9 67. 0 63.5 84.7 81.1 105.8 141.1
Electrical Data
Power Supply (V-Hz-Ph) 208/230-60-1
Min. Circuit Ampacity (A) 11.1 13.5 17 20.6 28.6 28 33.5
Max.Overcurrent
Protection (A)
15 20 25 35 50 45 50
Min/Max Voltage (V) 187/254
Min.Power Supply Cord AWG16 AWG14 AWG12 AWG12 AWG10 AWG10 AWG8
Dimension
Outline Dimension (W/D/H)
(inch)
21
1/2 / 21 1/2
/ 24
24 / 24 / 24 1/2 24 / 24 / 29 28 / 28 / 29 28 / 28 / 29 28 / 28 / 29
29 1/2 / 29 1/2
/ 33 1/2
Package Dimension
(W/D/H) (inch)
22 5/8 / 22 5/8 /
25 5/8
25 5/8 / 25 5/8 /
25 3/4
25 5/8 / 25 5/8 /
29 3/4
30 1/2 / 30 1/2 /
29 3/4
30 1/2 / 30 1/2 /
29 3/4
30 1/2 / 30 1/2 /
29 3/4
30 1/2 / 30 1/2 /
39 5/8
Weight
Net Weight (lb) 99.2 119.1 130.1 154.4 173.1 185.2 233.7
Gross Weight (lb) 105.8 1 2 7. 9 141.1 163.2 183 194 266.8
Mr Cool A/C Condenser
5