2.4 Installation Recommendations
NOTE: In some cases noise in the living area has been traced to gas pulsations from improper
installation of equipment.
1). Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb
customer.
2). Ensure that vapor and liquid tube diameters are appropriate for unit capacity.
3). Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4). Leave some slack between structure and unit to absorb vibration.
5). When passing refrigerant tubes through the wall, seal opening with RTV or other pliable
silicon--based caulk.(See Fig. 5.)
6). Avoid direct tubing contact with water pipes, duct work, oor joists, wall studs, oors, and
walls.
7). Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes
in direct contact with tubing. (See Fig. 5.)
8). Ensure that tubing insulation is pliable and completely surrounds vapor tube.
9). When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing
insulation. (See Fig. 5.)
10). Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of
insulation.
When outdoor unit is connected to factory--approved indoor unit, outdoor unit contains system
refrigerant charge good for 25 ft.
For proper unit operation, check refrigerant charge using charging information located on
control box cover and/or in the Check Charge section of this instruction.
NOTE: Avoid contact between tubing and structure
OUTDOOR WALL
CAULK
INDOOR WALL
LIQUID TUBE
INSULATION
VAPOR TUBE
JOIST
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
THROUGH THE WALL
INSULATION
VAPOR TUBE
LIQUID TUBE
SUSPENSION
1”MIN.
Fig.5 – Connecting Tubing Installation