Table 8. Normal Operating Pressures − Liquid +10 and Vapor +5 PSIG* (All Models)
(
) **
MHP13018 MHP13024 MHP13030 MHP13036
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
Heating
60(15) 346/139 352 / 138 338 / 137 350 / 134
50(10) 323/117 331/114 334/112 331/117
40(4) 306/98 304/99 312/93 313/97
30(-1) 278/84 299/80 302/74 298/83
20(-7) 273/66 283/66 280/53 284/66
Cooling
65(18) 226/140 233/137 238/138 220/138
70(21) 244/141 252/138 263/139 236/140
75(24) 263/142 271/140 279/139 256/141
80(27) 283/143 292/141 299/140 276/142
85(29) 302/144 314/142 324/141 298/143
90(32) 328/145 338/143 340/142 321/144
95(35) 351 / 146 361 / 145 375 / 145 344 / 144
100(38) 376 / 147 387 / 146 397 / 145 369 / 146
105(41) 402 / 148 412 / 147 424 / 147 394 / 147
110(43) 430 / 149 441 / 148 454 / 150 421 / 148
115(46) 465 / 150 471 / 151 485 / 150 449 / 149
*IMPORTANT—These are most popular match−up pressures. Indoor match up, indoor air quality, and
indoor load cause pressures to vary.
**Temperature of the air entering the outside coil.
(
) **
MHP13042 MHP13048 MHP13060
Liquid / Vapor Liquid / Vapor Liquid / Vapor
Heating
60(15) 373 / 139 355/130 351/117
50(10) 363/117 336/113 333/105
40(4) 348/97 315/88 316/88
30(-1) 336/74 296/72 308/70
20(-7) 322/64 286/64 300/61
Cooling
65(18) 223/125 231/136 243/136
70(21) 241/130 248/139 263/137
75(24) 261/134 271/140 282/138
For more details visit www.MrCool.com