Table 5
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 Temperature Rating
MORE THAN 100’ (30 METERS) 16 35°C Minimum
A Run 24VAC control wires through cutout with grommet.
B Run 24VAC control wires through wire tie.
C Make 24VAC control wire connections.
NOTE: Wire tie provides low voltage wire strain relief and to maintain separation
of eld low and high voltage circuits
NOTE: For proper voltages, select thermostat wire (control wires)gauge per
table above.
NOTE: Do not bundle any excess 24VAC control wires inside control box.
7.4 Unit High Voltage Connections
A Run HIGH VOLTAGE control wires through cutout with grommet.
B Make HIGH VOLTAGE control wires connections.
C Tighten wire tie to security HIGH VOLTAGE control wiring.
NOTE: Any excess high voltage eld wiring should be trimmed
and secured away from any low voltage eld wiring
NOTE: To facilitate a conduit, a cutout is located in the bottom of the control
box. Connect conduit to the control box using a proper conduit tting.
NOTE: The signal line of the wired controller must be separated from the power
line and the connecting line between the indoor unit and the outdoor unit.
Important Electric Data
Table 6
Model
Compressor
Fan
Motor
Fuse/Breaker
Capacity
Min. Power
Supply Cord
Power Supply Qty. RLA LRA FLA
V/Ph/Hz - A A A A AWG
MAC13018 208/230/1/60 1 7.9 38 1.2 15 AWG16
MAC13024 208/230/1/60 1 9.8 53 1.2 20 AWG14
MAC13030 208/230/1/60 1 12.6 71 1.2 25 AWG12
MAC13036 208/230/1/60 1 15.08 64 1.7 35 AWG12
MAC13042 208/230/1/60 1 21.5 105 1.7 50 AWG10
MAC13048 208/230/1/60 1 21 115 1.7 45 AWG10
MAC13060 208/230/1/60 1 25 150 2.1 50 AWG8
MHP13018 208/230/1/60 1 7.5 38 0.8 15 AWG16
MHP13024 208/230/1/60 1 9.8 53 1.2 20 AWG14
MHP13030 208/230/1/60 1 12.5 71 0.7 25 AWG12
For more details visit www.MrCool.com