15
testing procedure.
NOTE: The term absolute pressure means the total actual pressure within a given volume
or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to
atmospheric pressure minus vacuum pressure.
3). When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the
following:
● Close manifold gauge valves
● Close valve on vacuum pump
● Turn off vacuum pump
● Disconnect manifold gauge center port hose from vacuum pump
● Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150
psig (1034 kPa) and purge the hose.
● Open manifold gauge valves to break the vacuum in the line set and indoor unit.
● Close manifold gauge valves.
4). Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder.
Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.
5). Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to
evacuate the line set and indoor unit until the absolute pressure does not rise above 500
microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum
pump and closing the manifold gauge valves.
6). When the absolute pressure requirement above has been met, disconnect the manifold hose
from the vacuum pump and connect it to an upright cylinder of HFC−410A refrigerant. Open
the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor
unit.
7). Perform the following:
● Close manifold gauge valves.
● Shut off HFC−410A cylinder.
● Reinstall service valve cores by removing manifold hose from service valve.
Quickly install cores with core tool while maintaining a positive system pressure.
● Replace stem caps and secure nger tight, then tighten an additional one−sixth (1/6) of a turn
as illustrated.
7. Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric
Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian
Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application
diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent
protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power
(24VAC − 40 VA minimum).