Installation Guide
Page 6 of 9 507043-04Cmrcool.com
6. Measure  indoor  air  (entering  indoor  coil)  wet-bulb 
temperature with a sling psychrometer.
7. Compare superheat reading at service valve with the 
chart located on control box cover.
8. If  unit  has  a  higher  suction  line  temperature  than 
charted  temperature,  add  refrigerant  until  charted 
temperature is reached,
9. If  unit  has  a  lower  suction  line  temperature  than 
charted temperature, reclaim refrigerant until charted 
temperature is reached.
10. Remove charge if superheat is low and add charge if 
superheat is high.
Units with Indoor TXV
Units  installed  with  cooling  mode  TXV  require  charging 
with the subcooling method.
1. Operate unit a minimum of 10 minutes before checking 
charge.
2. Measure liquid service valve pressure by attaching an 
accurate  gage  to  service  port.  Determine  saturation 
temp. from T/P chart.
3. Measure  liquid  line  temperature  by  attaching  an 
accurate thermistor type or electronic thermometer to 
liquid line near outdoor coil.
4. Calculate  subcooling  (saturation  temp.  -  measured 
temp.)  and  compare  to  table  on  back  of  control  box 
cover. 
5. Add refrigerant if subcooling is lower than range shown 
in table. Recover refrigerant to decrease subcooling.
6. If ambient temp. is lower than 65° F, weigh refrigerant 
according to the name plate data.
NOTE: If a TXV is installed on indoor unit, a hard start kit will 
be required on all models with reciprocating compressors. 
are also  recommended for  areas with  utility power  lower 
than 208 Vac.
System Operation
The  outdoor  unit  and  indoor  blower  cycle  on  demand 
from  the  room  thermostat.  When  the  thermostat  blower 
switch  is  in  the  ON  position,  the  indoor  blower  operates 
continuously.