Installation Guide
507043-04C Page 5 of 9mrcool.com
Start-Up Procedure
1. Close electrical disconnects to energize system.
2. Set room thermostat at desired temperature. Be sure 
set point is below indoor ambient temperature.
3. Set the system switch of the thermostat on COOL and 
fan switch for continuous operation (ON) or AUTO, as 
desired.
4. Adjust  refrigerant  charge  per  “Adjusting  Charge” 
section.
Adjusting Charge
Factory charge is shown on the rating label located on the 
access panel.
All units are factory charged for 15 feet of connecting line 
set. Charge  should be adjusted for line set lengths other 
than 15 feet.  For  line  sets shorter than 15 feet in length, 
remove  charge.  For  line  sets  longer  than  15  feet,  add 
feet.  For  lines  longer  than  50  feet.,  refer  to  long  line  set 
guidelines.
Refrigeration Charge Adjustment
Liquid Line Diameter Oz. Per Linear Foot
3/8” 0.6
Table 2. 
350-450  CFM  per  ton  (12,000  Btuh)  through  a  wet  coil. 
Refer to indoor unit instructions for methods of determining 
Cooling Cycle Charge Adjustment Procedure
Units with Indoor Pistons
Units installed with indoor pistons require charging with the 
superheat method.
within ± 20 % of its rated CFM.
1. Operate unit a minimum of 10 minutes before checking 
charge.
2. Measure  suction  pressure  by  attaching  a  gage  to 
suction valve service port. Determine saturation temp 
from T/P chart.
3. Measure suction temperature by attaching an accurate 
thermistor  type  or  electronic  thermometer  to  suction 
line at service valve.
4. Calculate  superheat  (measured  temp.  -  saturation 
temp.).
5. Measure  outdoor  air  dry-bulb  temperature  with 
thermometer.
Remove access panel to gain access to unit wiring. Extend 
wires from disconnect through power wiring hole provided 
and into unit control box. Flexible conduit is required for the 
swing out control box feature.
The unit cabinet must have an uninterrupted or unbroken 
ground.  The  ground  must  be  installed  in  accordance 
with  all  electrical  codes. Failure  to  follow this  warning 
 WARNING
Connect ground wire to ground connection in control box 
for safety. Connect power wiring to contactor.
High voltage power connections to 3-phase models is made 
Contol Wiring
The control voltage is 24 VAC. NEC Class I insulated 18 
AWG is required for control wiring. For lengths longer than 
150 feet, contact your local distributor for technical service.
Ensure  the  room  thermostat  is  properly  installed  per 
instructions shipped  with  room  thermostat.  Generally  the 
thermostat  should  not  be  exposed  to  sunlight,  drafts  or 
vibration and should not be mounted on exterior walls.
Low voltage wiring must be separated from high voltage 
wiring.
 WARNING
Low voltage connections should be in accordance to the 
wiring diagram.
Figure 2. Typical Low Voltage Connection










