8.0 Condensate Considerations
Make provision for a condensate drain connection. Some installations require a condensate
pump to take the condensate to a suitable drain. It’s common practice to install extra tees near
the Geocool unit to allow access for pouring drain cleaner down the condensate drain. Insure all
extra openings are capped off or are plugged.
All Geocool vertical units have P-traps built internally in the units (see image below). These
units require a vent to be installed downstream and outside of the unit. Installation of a second
P-Trap is not necessary and if installed, will not allow the unit's condensate pan to drain
properly,
All Geocool Horizontal units are low profile. Due to this, they require standard P-Traps which
are vented on the leaving water side and located directly outside the unit (see image below).
Horizontal cabinets will need to be installed on a platform if not hanging in the air in order for a
P-trap to be installed.
Never tie the condensate drain and the discharge water line together due to the potential