All Geocool vertical units have P-traps built i nternally withi n the units (see i mage below). These
units require a vent to be i nstalled downstream and outside of the unit. Installation of a second P-
Trap is not necessary and if installed, will not allow the unit's condensate pan to drain
properly,
All Geocool Horizontal units are low profile. Due to this, they require standard P-Traps which
are vented on the leaving water side and located directly outside the unit (see image below).
Horizontal cabinets will need to be installed on a platform if not hanging in the air in order for a
P-trap to be installed.
Never tie the condensate drain and the discharge water line together due to the potential
for severe water damage.
A float switch i s factory i nstalled i nside the Geocool® drain pan . When this switch is triggered by
condensate backing up, will shut down the compressor and a RED status l ight l abeled
CONDENSATE FAULT will show up on the front panel display. The compressor will remain off
and the l ight i lluminated until the condensate clog has been cleared.