PERFORMANCE DATA (cont.)
ELECTRIC HEATER STATIC PRESSURE DROP (in wc)
FB4C
018 --- 036
FB4C
042 --- 061
HEATER
ELEMENTS
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
HEATER
ELEMENTS
kW
EXTERNAL STATIC
PRESSURE
CORRECTION
0 0 +.02 0 0 +.04
1 3, 5 +.01 2 8, 10 +.02
2 8, 10 0 3 9, 15 0
3 9, 15 –.02 4 20 –.02
4 20 –.04 6 18, 24, 30 –.10
The airflow performance data was developed using fan coils with 10---kW electric heaters (2 elements) in the 018 through 036 size units and
15--- kW heaters (3 elements) in the 042 through 061 size units. For fan coils with heaters of a different number of elements, the external avail-
able static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as ind icated ab ove.
MINIMUM CFM AND MOTOR SPEED SELECTION
FB4C
HEATER kW
3 5 8 9 10 15 18 20 24 30
018 525 525 525 — 600 — — — — —
024 & 025 700 700 700 — 700 775 — — — —
030 — 875 875 — 875 875 — 1060 — —
036 — 1050 970 970 970 920 — 1040 — —
042 — — 1225 1225 1225 1225 1225 1225 — —
048 — — 1400 1400 1400 1400 1400 1400 1400 1400
060 & 061 — — 1750 1750 1750 1750 1750 1750 1750 1750
Speed Tap 4 (white wire) is used for electric heat only. White wire must remain on tap 4.
ACCESSORY ELECTRIC HEATERS
HEATER
PART NO.
kW @
240V
VOLTS/
PH
STAGES (kW
OPERATING)
INTERNAL
CIRCUIT
PROTECTION
FAN COIL SIZE
USED WITH
HEATING CAP.**
@ 230V
KFCEH0401N03 3 230/1 3 None 018–025 9,400
KFCEH0501N05 5 230/1 5 None 018–061 15,700
KFCEH0801N08 8 230/1 8 None 018–061 25,100
KFCEH0901N10 10 230/1 10 None 018–061 31,400
KFCEH3201F20 20 230/1 5, 20 Fuse} 030–061 62,800
KFCEH1601315 15 230/3 5, 15 None 036–061 47,100
KFCEH2001318 18 230/3 6, 12, 18 None 042–061 56,500
KFCEH3401F24 24 230/3* 8, 16, 24 Fuse 048, 061 78,300
KFCEH3501F30 30 230/3* 10, 20, 30 Fuse 048, 061 94,100
KFCEH2401C05 5 230/1 5 Circuit Breaker 018–061 15,700
KFCEH2501C08 8 230/1 8 Circuit Breaker 018–061 25,100
KFCEH2601C10 10 230/1 10 C ircuit Breaker 018–061 31,400
KFCEH3301C20 20 230/1 5, 20 Circuit Breaker 030–061 62,800
KFCEH2901N09 9 230/1{ 3, 9 None 036–061 28,200
KFCEH3001F15 15 230/1 5, 15 Fuse} 024–061 47,100
KFCEH3101C15 15 230/1 5, 15 Circuit Breaker 024–061 47,100
*Field convertible to 1 phase.
{Field convertible to 3 phase.
}Single point wiring kit required for these heaters in Canada.
**Blower Motor heat not included.