Refrigerant Piping Connection
AFTER PERFORMING GAS LEAK CHECKS
After confirming that all the pipe connection 
points DO NOT leak, replace the valve cover 
on the outside unit.
Electrical and Gas Leak Checks
8
Gas Leak Checks
WARNING – RISK OF 
ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL,
STATE, AND NATIONAL ELECTRICAL CODES, 
AND MUST BE INSTALLED BY A LICENSED
ELECTRICIAN.
Electrical Safety Checks
BEFORE TEST RUN
DURING TEST RUN
After installation, confirm that all electrical wiring is 
installed in accordance with local and national 
regulations, and according to the Installation 
Manual.
Check Grounding Work
Measure grounding resistance by visual detection 
and with grounding resistance tester. Grounding 
resistance must be less than 4.
Note: This may not be required for some locations 
in the US.
Check for Electrical Leakage
During the Test Run, use an electroprobe and 
multimeter to perform a comprehensive electrical 
leakage test. 
If electrical leakage is detected, turn off the unit 
immediately and allow an electrician to find and 
resolve the cause of the leakage.
Note: This may not be required for some locations 
in the US.
There are two different methods to check for 
gaseous leaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid 
detergent to all pipe connection points on the 
indoor unit and outdoor unit. The presence of 
bubbles indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s opera-
tion manual for proper usage instructions.
9
Electrical and Gas Leak Checks