Installation Manual and Owner's Guide
Page 20mrcool.com
Indoor Unit Installation
Move to left or right
Fig. 5.10
1.2-1.95in
(30-50mm)
1.2-1.95in
(30-50mm)
Indoor Unit 
Installation
 CAUTION
Dents in the piping will affect performance. If you dent or damage the piping, cease 
manipulation immediately and contact MRCOOL technical support at (270) 366-0457.
Be extremely careful not to dent or damage the piping while bending them away from the unit. 
Fig. 5.4
Keep in mind that the hooks on the mounting 
plate are smaller than the holes on the back 
of the unit. If you find that you don’t have 
ample room to connect embedded pipes to 
the indoor unit, the unit can be adjusted left 
or right by about 30-50mm (1.25-1.95in), 
depending on the model.
UNIT IS ADJUSTABLE
Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating sleeve 
attached to the back of the unit. You must prepare 
the piping before passing it through the hole in the 
wall. Refer to the Refrigerant Piping Connection 
section of this manual for detailed instructions on 
torque requirements, technique, etc.
1. The piping will exit the unit from the right size of 
the air handler.
2. Connect the indoor refrigerant piping to the 
connective piping that will join the indoor and 
outdoor units.
3. Based on the position of the wall hole relative to 
the mounting plate, determine the necessary angle 
of your piping.
4. Grip the refrigerant piping at the base of the bend.
5. Slowly, with even pressure, bend the piping 
towards the hole. DO NOT dent or damage the 
piping during the process.
NOTE ON PIPING ANGLE
Refrigerant piping should exit the indoor 
unit from the right-hand side:
Refer to Fig. 5.4 for details.