Installation Manual
2
2
1
1000/39.4in
1000/39.4in
1000/39.4in
1000/39.4in
1000/39.4in
1000/39.4in
2500/98.4in
260/10.2in
290/11.4in
Ceiling height
Use installation hooks for installation. Check whether the 
ceiling is strong enough to support the weight of the indoor 
unit. If there is a risk, reinforce the ceiling before installing 
the unit.
Space required for installation see the figure below ( :air flow 
direction) 
1 Air inlet
2 Air outlet
Install this unit where the height of bottom panel is more than
8.2ft / 2.5m so that the user cannot easily touch.
2)
3)
4
Do not install the unit in an area where flammable materials 
are present due to risk of explosion resulting in serious 
injury or death.
DANGER
If the basis underneath the unit is not strong enough to 
support the weight of the unit, the unit could be fall out of 
place and cause serious injury.
WARNING
 Select an installation site where the following conditions are 
 fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can be 
 ensured.
- Where there is no risk of flammable gas leaking.
- The equipment is not intended for use in a potentially explosive 
 atmosphere.
- Where piping between indoor and outdoor units is possible 
 within the allowable limit.(Refer to the installation manual of the 
 outdoor unit.)
- Keep indoor unit, outdoor unit, inter unit wiring and remote 
  control wiring at least 3.3 feet away from televisions and 
 radios.This is to prevent image interference and noise in those 
 electrical appliances.(Noise may be generated depending on 
 the conditions under which the electric wave is generated,even 
 if 3.3ft is kept.)
- When installing the wireless remote control kit, the distance 
 between wireless remote control and indoor unit might be 
 shorter if there are fluorescent lights who are electrically started 
 in the room.The indoor unit must be installed as far as possible 
 away from fluorescent lights. 
1.1 Selecting installation site
00
When the conditions in the ceiling are exceeding 30 C / 86 F and a 
relative humidity of 80%, or when fresh air is inducted into the ceiling, 
an additional insulation is required (minimum 0.4in / 10mm thickness,
polyethylene foam).
1)
1. INDOOR UNIT INSTALLATION
Unit: mm
For more info visit www.mrcool.com