Installation Manual
- Attach the hanger bracket to the suspension bolt. Be sure to 
 fix it securely by using a nut and washer from the upper and 
 lower sides of the hanger bracket.
- Securing the hanger bracket see figure below.
2) Fix the paper pattern for installation. (For new ceilings only)
1) Install the indoor unit temporarily.
1 Nut (field supply)
2 Washer (field supply)
3 Hanger bracket
4 Double nuts (field supply,tighten)
1.3 Install the indoor unit
When installing optional accessories, read also the installation 
manual of the optional accessories. Depending on the field 
conditions, it may be easier to install optional accessories before 
the indoor unit is installed (except for the decoration panel).
However, for existing ceiling, install fresh air inlet component kit
and branch duct before installing the unit.
- The paper pattern for installation corresponds with the 
 measurements of the ceiling opening. Consult the builder for 
 details.
- The center of the ceiling opening is indicated on the paper
 pattern for installation.
- After removing the packaging material from the paper patten for 
 installation, attach the paper pattern for installation to the unit 
 with the attached screws as shown in figure below.
3) Adjust the unit to the right position for installation.
(Refer to the chapter "Preparations before installation" on page 5.)
1 Paper pattern for installation(on some models)
2 Center of the ceiling openiing
3 Screws(supplied with the decoration panel)
1
2
3
4
1
2
3
- Do not install the unit tilted. The indoor unit is equipped with a 
 built-in drain pump and float switch. (If the unit is tilted against 
 the direction of the condensate flow (the drain piping side is 
 raised), the float switch may malfunction and cause water to 
 drip.)
- Check if the unit is levelled at all four corners with a water level 
 or a water-filled vinyl tube as shown in figure below. 
4) Check if the unit is horizontally levelled.
1 Water level
2 Vinyl tube
5) Remove the paper pattern for installation. (For new ceiling
 only).
1
1
2
2
6
For more info visit www.mrcool.com