Outdoor Unit Installation
Fig. 5.6
ALL WIRING MUST PERFORMED STRICTLY IN 
ACCORDANCE WITH THE WIRING DIAGRAM 
LOCATED INSIDE THE OUTDOOR UNIT’S WIRE 
COVER.
1.
Prepare the cable for connection:
USE THE RIGHT CABLE 
BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE 
MAINPOWER TO THE SYSTEM.
2. Remove the electrical wiring cover from the unit by
 loosening the 3 retaining screws. Refer to Fig. 5.6.
3. Remove the caps on the conduit panel.
4. Temporarily mount the conduit tubes (not
 included) on the conduit panel. 
5. Properly connect both the power supply and low
 voltage lines to the corresponding terminals on
 the terminal block.
6. Ground the unit in accordance with local codes.
7.  Be sure to size each wire so that it allows for it to
 be several inches longer than the required length
 for wiring.
8.  Use lock nuts to secure the conduit tubes.
9. Replace the wire cover and reinstall the 3 screws. 
•
 See table below for gauge requirements
G
Wire Cover 
Terminal block
Conduit panel
Connecting cable 
Power supply cord 
Please select the appropriate through-hole 
according to the diameter of the wire.
Over 1.57 in.(40 mm)
North America
Appliance
Amps (A)
AWG
20
20
15
9K
12K
9K
Model
Capacity
(BTU/hr)
Minimum Wire Gauge for Power Cables
MCA MOP  Min.  Pref.
14
14
14
12
12
14
15
15
10
1512K 14 1215
2018K 14 1215
25
3536K
24K 12
10
10
8
20
25
115V
208/
230V