Installation Manual
 Page 11 mrcool.com
Indoor Unit Installation
Refer to the following diagram to ensure proper distance from walls and ceiling:
Step 2: Attach mounting plate to wall
The mounting plate is the device on which you will 
mount the indoor unit
.
1. Remove the screw that attaches the mounting
 plate to the back of the indoor unit.
2. Place the mounting plate against the wall in a 
 location that meets the standards in the
 Select Installation Location step.  (See
 Mounting Plate Dimensions for detailed
 information on mounting plate sizes.)
3. Drill holes for mounting screws in places that:
•
  have studs and can support the weight of 
 the unit 
 •
 correspond to screw holes in the mounting
 plate
4. Secure the mounting plate to the wall with the 
 screws provided.
5.
  Make sure that mounting plate is flat against 
 the wall.
NOTE FOR CONCRETE OR BRICK WALLS:
If the wall is made of brick, concrete, or similar 
material, drill 0.2 in diameter (5 mm diameter)
holes in the wall and insert the sleeve anchors 
provided. Secure the mounting plate to the 
wall by tightening the screws directly into the 
clip anchors.
Step 3: Drill wall hole for connective piping
You must drill a hole in the wall for refrigerant piping, 
the drainage pipe, and the signal cable that will 
connect the indoor and outdoor units.
1. Determine the location of the wall hole based on 
 the position of the mounting plate. Refer to 
 Mounting Plate Dimensions on the next page 
 to help you determine the optimal position. Refer 
 to Fig. 4.3 wall hole diameter and install at a slight
 angle to facilitate drainage.
2. Using a core drill [3.5 in (76.2 mm) for 24K & 36K
 units, 2.5 in (65 mm) for all others], drill a hole in 
 the wall. Make sure that the hole is drilled at a 
 slight downward angle, so that the outdoor end of 
 the hole is lower than the indoor end by about 0.2 
 to 0.275 in (5 mm-7 mm). This will ensure proper 
 water drainage. (See Fig. 4.2)
3.  Place the protective wall cuff in the hole. This
 protects the edges of the hole and will help seal 
 it when you finish the installation process.
Fig. 4.1
 CAUTION
When drilling the wall hole, be sure to avoid 
wires, plumbing, and other sensitive 
components.
Minimum Ceiling
Clearance is
5.9 in (15cm)
>4.75 in
(12 cm)
>4.75 in
(12 cm)
For Ceilings GREATER
Than 9 Foot, Suggested 
Floor Clearance is
90.55 in (230 cm)
For Ceilings LESS
Than 9 Foot, Suggested 
Floor Clearance is
78.55 in (200 cm)
NOTE: When the gas side connective pipe is 
5/8 in (16 mm) or more, the wall hole should 
be 3.54 in (90 mm). 
Screw