Installation Manual
Page 32mrcool.com
Testing
DOUBLE-CHECK PIPE CONNECTIONS
IF AMBIENT TEMPERATURE IS BELOW 
63°F (17°C)
5. After the Test Run is successfully complete, and
 you confirm all check points in List of Checks to
 Perform have PASSED, do the following: 
 a. Using remote control, return unit to normal
 operating temperature.
 b. Using insulation tape, wrap the indoor
 refrigerant pipe connections that you left
 uncovered during the indoor unit installation
 process.
Fig. 9.1
Manual control button
During operation, the pressure of the refrigerant 
circuit will increase. This may reveal leaks that were 
not present during your initial leak check. Take time 
during the Test Run to double-check that all 
refrigerant pipe connection points do not have leaks. 
Refer to Gas Leak Check section for instructions.
You cannot use the remote controller to turn on 
the COOL function when the ambient 
temperature is below 63°F. In this instance, you 
can use the MANUAL CONTROL button to test 
the COOL function.
1. Lift the front panel of the indoor unit, and 
raise it until it clicks in place.
2. The MANUAL CONTROL button is located 
on the right-hand side of the unit. Press it 2 
times to select the COOL function. See Fig.9.1.
3. Perform Test Run as normal.