Installation Sheet
Installing a Remote Temperature Probe
REMOTE TEMPERTURE PROBE
1. The probe must be installed:
a. On a vertical surface.
b. 4-5’ above the floor.
Locate the probe in a location representative of the desired
steambathing temperatures. Do not locate the probe above or near
the steam head or direct steam emissions. The probe has an integral
20 ft. cable. Ensure that the probe and iSteam control are located
accordingly.
2. Drill a 1/4” hole in the wall. Do not oversize or undersize the
hole. Clean area thoroughly.
3. Route the end of the temperature probe cable with the
temperature probe through the wall into the steam room as shown
in Diagram 1.
IMPORTANT NOTE: Do not strain, staple, pinch or otherwise
damage the probe cable.
4. With a minimal length of the cable exposed apply silicone
(provided) to the hole in the wall as required to create a moisture
seal as shown in Diagram 2.
5. Push the iMSTS cable and probe into the hole as required
to leave between 1/4”- 1/2” of the probe. Exposed as shown in
Diagram 3.
6. Insure a minimum of 1/4” of the probe is exposed to the air.
Failure to do so may result in an inoperative control and a
hazardous condition. The exposed area of the probe must be free of
silicone or any materials that prevent direct exposure to the steam
room air. Failure to do so may interfere with the ability to sense
temperature and may result in excessive steam room temperatures.
The Remote Temperature Probe is required when a steam control is installed outside the steam room.