Use and Care Manual

5
Installation Instructions and Owner’s Manual
Gas Fired Infrared Space Heater
Figure 4 connection diagram
9. VENTILATION
a. Theminimumintakeandexhaustairopeningsshallprovide
fornotlessthan400CFMforevery100,000BTUinputexcept
thattheinfiltrationareamaybeincludedintheintakearea.
b. Wherenatural(gravity)ventilationisprovidedforexhaust,the
openingsmustbedistributedabovetheheaters(preferablyat
thepeakoftheroof)andtheareasofopeningsshallnotbe
lessthan300squareinchesforevery100,000BTUinput.
Figure 5. Thermostate controls
10. START-UP PROCEDURE
OPENTHEGASSUPPLYVALVEORVALVES
SetthethermostattotheOFFposition.SeeFigure5.Ifthe
manualgascontrolknobonthegasvalveisnotintheOFF
position,partiallydepresstheknobandrotatetotheOFFposition.
SeeFigure6.
Wait5minutestoallowgasthatmayhaveaccumulatedinthe
mainburnertoescape(especiallyimportantafterinstallation).
TurnthemanualgascontrolknobtothePILOTposition.
Depressthemanualgascontrolknob.Usingamatch,lightthe
pilotlight.SeeFigure6.Holdtheknobdownforapproximately
30secondstoallowanyairingaslinestopassthroughpilotand,
oncethepilotislit,allowthethermocoupletoheatupenoughto
MANUALGAS
CONTROLKNOB
WRENCH
BOSS
GASINLET
PRESSUREREGULATOR
ADJUSTMENT
STANDARD
PRESSURE
REGULATOR
(Incomingpressure
notexceed14”W.C.)
PILOTGAS
OUTLET
(PRESSURE
TAPPING
DIRECTLY
BENEATH)
PILOTFLOW
ADJUSTING
SCREW
(BENEATH
COVERSCREW)
PILOTSTATPOWER
UNIT
Figure 6. Gas Valve
Components
activatethesafetyvalveinanopenposition.
ReleasemanualgascontrolknobandturntoON.Reset
thermostattodesiredtemperature.
NOTE:
DuringtheinitialstartupofMR.HEATERanodorand,perhaps,
somevaporwillcomefromtheheater.Thisisthegasketbinding
materialemittingthisodorand/orvapor.Afterapproximately20
minutesthisodorwilldisappearandnotoccuragain.
11. SHUTDOWN
1. TurnthermostattoOFF.
2. TurnmanualgascontrolknobongasvalvetoPILOTposition.
3. PartiallydepressknobandrotatetotheOFFposition.
4. Closegassupplyvalves.
12. OPERATOR MAINTENANCE
INSTRUCTIONS
1. TROUBLESHOOTING
a. Table4liststhecommonmalfunctionswhichyoumayfind
duringtheoperationormaintenanceofyourheater.
b. ForadditionalinformationrefertoHoneywellFieldBulletin
enclosedintheheatercarton.
c. Intheevent,resultscannotbeobtainedafterperformingall
listedsolutions,callyourMr.Heaterdealer,orthefactory
customerservicedepartmentat1-800-251-0001.
2. ADJUSTING THE PILOT FLAME
Thepilotflameshouldenvelope3/8to½in.(10to13mm)ofthe
tipofthethermocoupleorgenerator.Toadjustthepilotflame,
refertoFigure7.
a. Removepilotadjustmentcoverscrew.RefertoFigure8.
b. Turninneradjustmentscrewclockwisetodecreaseorcounter-
clockwisetoincreasepilotflame.
THERMOCOUPLE
PROPERFLAMEADJUSTMENT
3/8TO½INCH
(10TO13MILLIMETERS)
Figure 7. Proper flame adjustment
POWERPILEGASVALVE
POWERPILEGENERATOR
WIRE
SIZES
MAXIMUM
LENGTH
2WIRE
CABLE
NO.18
NO.16
NO.14
15FEET
30FEET
50FEET
CAUTION:
Neverconnectpowerpilegas
valveorthermostattolinevoltage
oratransformer
FactoryWired
ThermostatWires