SECTION 3 VTG-IOM-2012-1001 OPERATION
4 WARNING
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
Operating this equipment beyond
its design limits can damage the
equipment and can be dangerous.
Do not operate the equipment
outside of its limits. Do not try to
upgrade the equipment performance
through unapproved modi cations.
Unapproved modi cations may
cause injury, equipment damage, and
will void the warranty.
Access to Variable Speed Drive Blower Motor
(Models VTG-3000LE, VTG-4000LE)
NOTE: ´ Some Fulton Vantage Low Emissions Designs include a Variable Frequency
Drive (VFD). The VFD is a Telemechanique Altivar 21 style.
The Variable Speed Drive programs are password protected and should only be
accessed by factory-trained personnel. Please contact your authorized Fulton
representative for assistance.
¡ Test of Ignition Safety System
Test the ignition system safety shuto as follows:
1. Remove the black plug/connector from the main gas valve (it is held on
with a central screw).
2. With the main gas cock (inlet manual gas valve) open, the burner should
be cycled on. After all the safety limits such as gas pressure, water ow and
temperature are satis ed, the blower will run and pre-purge the boiler.
3. Once the purge is complete (30 seconds), the ignition transformer will be
energized. There will be a 4 second trial for ignition period. During this
period, indicator lights on the ame safeguard (pilot and main)
4. The main gas valve will not open because there is no power to the valve
due to the disconnected wires. Hence, no  ame will be established and the
ame safeguard will not receive a  ame signal from the UV scanner.
5. After 4 seconds, the ame safeguard programmer will assume a “Flame
Failure condition and go to a “lockout” mode. Lockout will require manual
reset of the ame safeguard.
6. After completing this test, turn o the boiler and reconnect the wires to
the main gas valve.
Perform Test of Low Water Cut Off
Once the boiler is full of water the following test can be accomplished:
1. Turn the boiler on, this will start the Call for Heat sequence.
2. Press and hold the Low Water Test button for 3 seconds. The Low Water
light should illuminate and the boiler should shut down the Call for Heat
sequence.
3. Reset the Low Water condition by pressing the Low Water reset button and
the LMV Reset button. Boiler should start the Call for Heat sequence again.
4. Perform appropriate test for any secondary Low Water controls.