Specifications

© The Fulton Companies 2012
3-12
OPERATION VTG-IOM-2012-1001 SECTION 3
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
4 CAUTION
The minimum return water
temperature to the boiler is 14F (6C)
when ring on oil. Failure to maintain
this will void the warranty.
Unburned oil, unlike gas, does not leave
the combustion chamber during purge.
A temperature exceeding 120°F** in
the boiler room may cause premature
failure of electrical components.
Provisions should be made to maintain
an ambient temperature of 120°F** or
less (the panel box interior should not
exceed 12F**).
**Pumps, PLC or ModSync panels may
require lower ambient temperatures or
additional cooling.
§ Min. Loop Temp: Minimum setpoint temperature at which the boiler can
operate.
§ Max. Loop Temp: Maximum setpoint temperature at which the boiler can
operate.
§ SC-500 Setpoint: Boiler setpoint when SC-500 setpoint mode is selected.
} SET BOILER ON TEMPERATURE
1. From Main Menu screen, select System Con g.
2. Select Sensor Con g and set.
} SET PROPORTIONAL BAND, INTEGRAL AND DERIVATIVE VALUES
The Proportional Band, Integral, and Derivative Values are accessed via the PID
Con guration Screen.
§ Proportional Band: This is the percentage of change in proportion to the
di erence between setpoint (SP) and process output (PV).
§ Integral: The integral is a variable time period used to adjust an output.
§ Derivative: This variable allows the anticipation of whether the PV will
overshoot the SP, and reduces the output as needed.
§ Manual Reset: This value will o set the PID.
¡ Yokogawa UT 32A Basic Programming:
} CHANGE SET POINT
1. SP (set point) display reads current set point in degrees F.
2. Use arrow keys on main screen to change SP to desired value. Press SET/
ENT to enter value.
} SET BOILER ON TEMPERATURE
1. Push and hold SET/ENT button for 3 seconds. Display will read oP.PA.
2. Push SET/ENT button. A1 will be displayed.
3. Enter value of subtractive di erential i.e. SP - A1= Heater On Temperature.
Ex. SP = 200, A1 = 5 Heater will turn on at 195 F. (Note: subtracting a
negative value yields a positive number. Ex. SP = 200, A1 = -5, Heater
will turn on at 205 F.
4. Push and hold SET/ENT button for 3 seconds. Display will return to default.
} SET BOILER OFF TEMPERATURE
1. Push and hold SET/ENT button for 3 seconds. Display will read oP.PA.
2. Use down arrow key to scroll to St.UP.