Specifications
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2 VTG-IOM-2012-1001 INSTALLATION
2-23
1/4" TAPPING FOR WATER
100 PSI MAXIMUM
ROOF
SUPPORT
4FT 3 IN
( 130 CM )
ADJUSTABLE
FLASHING
PVC PIPE
RISE TO RUN: 1/4" PER FOOT
METAL PLATE
FIRE STOP
MIN 4FT / 122 CM
ABOVE AIR
INTAKE PIPING
ADJUSTABLE
FLASHING
ADHESIVE SEAL
STORM COLLAR
SCREENED INLET
IF SNOW ACCUMULATION
IS APPLICABLE, OPENING TO BE
1 FT. / 30 CM ( MIN. ) ABOVE
THIS NORMALLY EXPECTED LEVEL.
TYPICAL ROOF PENETRATIONS
( SUGGESTED TERMINATION CONFIGURATIONS )
INSTALL SUPPORT STRAPS AT
5FT / 152CM HORIZONTAL
INTERVALS AND AT ELBOWS
EXHAUST
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
STAINLESS STEEL
HIGH TEMPERATURE
EXHAUST PIPE & FITTINGS
VANTAGE
HYDRONIC
BOILER
( SIDE VIEW )
NOTE:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS.
AIR INLET
MAINTAIN MIN 9" / 22.86 CM
AIR SPACE CLEARANCES
TO COMBUSTABLES,
WIRES AND INSULATION
PVC
90° ELBOW
FIGURE 12 ROOF PENETRATION DETAILS