Specifications

© The Fulton Companies 2012
INSTALLATION VTG-IOM-2012-1001 SECTION 2
2-16
Figure 9 Notes
Characteristic Connection
1
Suction 3/8 NPT (Piped in the Field)
2
Return 3/8 NPT (Piped in the Field)
3
Pressure Gauge Attachment G 1/8 (Completed at Factory)
4
Vacuum Gauge Attachment G 1/8 (Completed at Factory)
5
Pressure Regulator
6
Outlet to Burner ¼” NPT (Completed at Factory)
Minimum Delivery Rate at 174
PSI Pressure
54 GPH
Delivery Pressure Range 145290 PSI
Maximum Suction 13 Hg
Oil Viscosity Range 2.8 75 cSt
Maximum Fuel Oil
Temperature
140 F
Maximum Suction and Return
Pressure
29 PSI
Pressure Calibration at the
Factory
198-200 PSI
Filter Mesh Width 0.006 Inches
FIGURE 9  OIL PUMP DETAILS
FIGURE 8  OIL PUMP LOCATION