Specifications
© The Fulton Companies 2012
INSTALLATION VTG-IOM-2012-1001 SECTION 2
2-16
Figure 9 Notes
Characteristic Connection
1
Suction 3/8” NPT (Piped in the Field)
2
Return 3/8” NPT (Piped in the Field)
3
Pressure Gauge Attachment G 1/8” (Completed at Factory)
4
Vacuum Gauge Attachment G 1/8” (Completed at Factory)
5
Pressure Regulator
6
Outlet to Burner ¼” NPT (Completed at Factory)
Minimum Delivery Rate at 174
PSI Pressure
54 GPH
Delivery Pressure Range 145 – 290 PSI
Maximum Suction 13 “ Hg
Oil Viscosity Range 2.8 – 75 cSt
Maximum Fuel Oil
Temperature
140 F
Maximum Suction and Return
Pressure
29 PSI
Pressure Calibration at the
Factory
198-200 PSI
Filter Mesh Width 0.006 Inches
FIGURE 9 OIL PUMP DETAILS
FIGURE 8 OIL PUMP LOCATION