INSTALLATION VTG-IOM-2012-1001 SECTION 2
2-12
FIGURE 5 CONDENSATE DRAIN PIPING FOR VANTAGE BOILERS
Figure 5 Notes:
§ Header must be level or slightly pitched toward the drain.
§ Header material to be galvanized steel or 316L stainless.
§ Header should be taken to the lowest point possible and at
least 5.5 inch drop from 1.5 inch condensate drain kit/trap
outlet.
§ 1.5 inch condensate drain kit/trap outlet is never to be
above 1 inch boiler condensate outlet.
§ For multiple boiler installation, maintain and minimum pipe
size of 1 inch for the header piping.
§ The maximum number of units to attach per condensate
drain kit is 12mm BTU total.
Detail A
0.25” TAPPING PROVIDED
FOR WATER CONNECTION
TO MAINTAIN WATER SEAL
5.5” MINIMUM
SIDE VIEW
Detail A
(condensate drain kit)