LCD MENU SETTINGS
CD MENU SETTINGSCD MENU SETTINGS
CD MENU SETTINGS
I / P Voltage Range Setting
Default : Input Voltage : LO = 170V,HI = 270V. Input Frequency : 45Hz~ 70Hz
LO : 120V ~ 200V( One Touch: +/- 1V)
HI : 250V ~ 280V( One Touch: +/- 1V)
1. Return point= +/_ 10V from the transfer point.
2. Press Enter to enable the setting. No need to re-start the inverter.
O/P Voltage /Frequency Setting
Default: 220VAC , 50HZ
Voltage: 220VAC / 230VAC / 240VAC Selectable
Frequency: AC= Synchronized to AC., DC= 50HZ / 60HZ Selectable
Press Enter to confirm. *NEED TO RESTART INVERTER.
AC/DC Prior Setting Functioning only under AC Mode. *This feature requires minimum 24V.
Default: AC Prior.
Select "AC MODE" for AC Prior ., "INVERTER MODE" for DC Prior.
1. Under “DC Prior” if battery voltage is too low, it will auto change to AC if AC normal.
2. Press Enter to confirm. *NEED TO RESTART INVERTER.
Battery Shutdown Voltage & Current Setting ( 48V/ 24V)
Default: 40V(20V).
HIGH: 42V ( 21V)/ MIDDLE: 40V ( 20V) / LOW :38V ( 19V) Selectable
1. Low Voltage warning point: 42.5 V( 21.5V)
2. Press Enter to enable the setting. No need to re-start the inverter.
Battery Charging Current Setting
Default: Middle
LOW ( 100AH) - MIDDLE ( 300AH) - HIGH ( 600AH)
Press Enter to enable the setting. No need to re-start the inverter.
(OPTIONAL
(OPTIONAL(OPTIONAL
(OPTIONAL, extra charge
, extra charge, extra charge
, extra charge)
))
) Green Power On/Off Setting
Green Power On/Off Setting Green Power On/Off Setting
Green Power On/Off Setting *
**
*R
RR
Requires minimum 24V & only under Inverter Mode.
equires minimum 24V & only under Inverter Mode.equires minimum 24V & only under Inverter Mode.
equires minimum 24V & only under Inverter Mode.
Default: Off.
Green Power Off: System running continuously.
Green Power On: System Auto Shutdown when Load < Pre-setting
Press Enter to enable the setting. No need to re-start the inverter.
(OPTIONAL
(OPTIONAL(OPTIONAL
(OPTIONAL, extra charge
, extra charge, extra charge
, extra charge) Green Power Mode
) Green Power Mode) Green Power Mode
) Green Power Mode
& Time Setting
& Time Setting& Time Setting
& Time Setting
*
**
*R
RR
Requires minimum 24V.
equires minimum 24V.equires minimum 24V.
equires minimum 24V.
Default: Time period for next detecting: 30 Sec.
Time: 15 Sec., 30 Sec., 45 Sec. 60 Sec selectable.
1. Detecting load: ~20w
2. When the load is less than 20w,the inverter will auto turn off and count the pre-set time ( 30 Sec.), then,
re-start.
3. Press Enter to enable the setting. No need to re-start the inverter.